Download Print this page

Mitsubishi Electric PURY-M200YNW-A1 Service Handbook page 168

Hide thumbs Also See for PURY-M200YNW-A1:

Advertisement

[6-3 Evaluating and Adjusting Refrigerant Charge ]
6-3-3
Maximum refrigerant charge
There is a limit to the amount of refrigerant that can be charged into a unit. Observe the maximum refrigerant charge in the
table below.
M200-500YNW-A1
Total index of the outdoor units
Factory charge (kg)
Maximum additional refrigerant
charge on site (kg)
Maximum refrigerant charge (kg)
EM200-500YNW-A1
Total index of the outdoor units
Factory charge (kg)
Maximum additional refrigerant
charge on site (kg)
Maximum refrigerant charge (kg)
6-3-4
Refrigerant Charge Adjustment Mode
On the model of unit described in this document, the refrigerant charge cannot be adjusted.
BS_06_F2
M200
M250
M300
5.2
5.2
5.2
13.5
13.5
15.5
18.7
18.7
20.7
EM200
EM250
EM300
5.2
5.2
5.2
13.5
13.5
15.5
18.7
18.7
20.7
M350
M400
M450
8.0
8.0
10.8
15.5
19.5
19.5
23.5
27.5
30.3
EM350
EM400
EM450
8.0
8.0
10.8
15.5
19.5
19.5
23.5
27.5
30.3
M500
10.8
19.5
30.3
EM500
10.8
19.5
30.3