Download Print this page

Mitsubishi Electric PURY-M200YNW-A1 Service Handbook page 380

Hide thumbs Also See for PURY-M200YNW-A1:

Advertisement

[8-13 Parts Replacement Instructions (Outdoor Unit) ]
(9) Remove the fan guard by unscrewing the 12 screws. (See Figure 7.)
(10) Insert a spacer between the control box and the heat exchanger.
(11) Remove the motor ASSY by unscrewing the 16 screws, using caution not to damage the motor wiring or the fan.
(See Figure 8.)
Figure 7
(12) Remove the front pillar by unscrewing the 7 screws. (See Figure 9.)
(13) Disconnect the TH7 sensor holder from the front pillar. (See Figure 9 Rear.)
(14) Remove the TH7 wiring from the heat exchanger by cutting the cable tie. (See Figure 10.)
Front pillar
Figure 9
BS_08_L
Fan guard
Front heat exchanger
Spacer *
Control box
*Use the supplied spacers.
Use the spacers 60 (D) x 250 (W) x 60 (H) when replacing the heat
exchangers for the maintenance of the accumulator and the pipes.
Front heat
exchanger
Connector
Front pillar
TH7
Rear
Spacer *
Motor ASSY
Figure 8
Remove the TH7 wiring from
the front heat exchanger.
Spacer *
Figure 10
Fan
TH7
Cable tie