Download Print this page

Mitsubishi Electric PURY-M200YNW-A1 Service Handbook page 136

Hide thumbs Also See for PURY-M200YNW-A1:

Advertisement

[5-1 Dipswitch Functions and Factory Settings ]
(2) Fan board
Switch
SW1
1
Enabling/Disabling no-load opera-
tion
No-load operation will continue for
approximately 30 seconds, and
then the unit will come to an ab-
normal stop. For details, refer to
the following page(s). [8-10-9
Checking the Fan Board for Dam-
age at No Load]
2
3
4
Only the addresses are preset before shipment (All other switches are set to OFF.) Unless otherwise specified, leave the
switch to OFF where indicated by "-," which may be set to OFF for a reason.
To set the address for a unit with one fan, only set SW1-3 to ON (= address 5). To set the addresses for a unit with two fans,
set SW1-3 on the fan board on the right side (when seen from the front of the control box) to ON (= address 5) and set SW1-
4 on the left fan board to ON (= address 6).
Leave SW1-1 to OFF during normal operation. Setting this switch to ON will disable the error detection function and may result
in equipment damage.
BS_05_M
Function
-
Address setting.
See the notes below.
Function according to switch
setting
OFF
ON
No-load oper-
No-load oper-
ation disabled
ation enabled
-
-
0
5
0
6
Switch setting timing
Anytime after power on
-
Before power on
Before power on
chapter 5 -
5

Hide quick links:

Advertisement

loading