Download Print this page

Error Code [1301] - Mitsubishi Electric PURY-M200YNW-A1 Service Handbook

Hide thumbs Also See for PURY-M200YNW-A1:

Advertisement

[7-3 Error Code Definitions and Solutions: Codes [1000 - 1999] ]
7-3-2

Error Code [1301]

1. Error code definition
Low pressure fault
2. Error definition and error detection method
When starting the compressor from Stop Mode for the first time if low pressure reads 0.098MPa [14psi] immediately before
start-up, the operation immediately stops.
3. Cause, check method and remedy
(1)
Inner pressure drop due to a leakage.
(2)
Low pressure sensor failure
(3)
Short-circuited pressure sensor cable due to
torn outer rubber
(4)
A pin on the male connector is missing.
(5)
Disconnected wire
(6)
Failure of the low pressure input circuit on the
controller board
When a shut-off valve is installed as a safety measure, closing of the valve may cause this error.
12
- chapter 7
Cause
Check method and remedy
Refer to the following page(s). [8-5-3 Comparing the Low-
Pressure Sensor Measurement and Gauge Pressure]