[5-1 Dipswitch Functions and Factory Settings ]
1)
To change the settings, set SW6-10 to ON, set SW4, and press and hold SWP3 for 2 seconds or longer (OFF ↔ ON).
LED3 will light up when the switch setting is ON, and lights off when OFF.
Use the LED3 display to confirm that the settings are properly made.
The settings will need to be set again when the control board is replaced. Write down the settings on the electrical wiring drawing label.
2)
For details, refer to the following page(s).[5-2-6 Defrost Operation Control]
3)
The table below shows how the target evaporation temperature is set with SW4 (982).
SW4(982)
Target evaporating
temperature
*SW4 (982) setting will not automatically be restored after the control board is replaced. (The function of SW4 is explained in Note 5.) When using the
function of SW4, write down the SW4 (982) setting on the control board panel, and manually reset the setting after the control board is replaced.
4)
Unless otherwise specified, leave the switch to OFF where indicated by "-" or where the cells are blank, which may be set to OFF for a reason.
5)
The settings that are configured with SW4 (SW6-10: ON) will automatically be stored on the indoor units that support the new function*. The stored
settings will automatically be restored when the outdoor unit control board is replaced. Not applicable to SW4 (982).
If none of the connected indoor units supports the new function, no configuration information will be saved. If this is the case, manually record the
settings configuration on the control box panel.
*The new function is supported on most units that are manufactured in December of 2012 and later. Depending on the model, this function may be
added on later date. Ask your dealer for further details.
6)
The table below shows the modes selectable with the function switches SW (997) and SW4 (1006).
Switch
SW4(997)
OFF
ON
7)
The table below shows the combinations of the settings for items No. 897 and No. 900 and the target evaporating temperature setting that corresponds
to each combination.
Switch
No.897
OFF
ON
8)
The table below shows the combinations of the settings for items No.885 and No.886 and the ratio of outdoor unit fan speed at low outside temperature
heating setting that corresponds to each combination.
Switch
No.885
OFF
ON
9)
Shaded areas (
) indicate factory settings.
4
- chapter 5
OFF   →   ON   →   OFF   →   ON   →   OFF   →   ON
0
-2
0
[32
]
[28
]
[32
]
SW4(1006)
OFF
50% mode
85% mode
No.900
OFF
0°C [32°F]
6°C [43°F]
No.886
OFF
Max
High
-4
0
-6
[25
]
[32
]
[21
]
ON
60% mode
70% mode
ON
9°C [48°F]
14°C [57°F]
ON
Middle
Low
BS_05_M