[2-8 Example System with an ME Remote Controller ]

2-8

Example System with an ME Remote Controller

2-8-1
System with a Connection of System Controller to Centralized Control
Transmission Line
(1) Sample control wiring
HU
52
TB3
M1 M2 S
HU
55
TB3
M1 M2 S
(2) Cautions
1)
ME remote controller and MA remote controller cannot both be
connected to the same group of indoor units.
2)
No more than 2 ME remote controllers can be connected to a
group of indoor units.
3)
Do not connect the terminal blocks (TB5) on the indoor units that
are connected to different outdoor units with each other.
4)
Replacement of male power jumper connector (CN41) must be
performed only on one of the outdoor units (not required if power
to the transmission line for centralized control is supplied from a
controller with a power supply function, such as AE-200E).
5)
Provide an electrical path to ground for the S terminal on the ter-
minal block for centralized control (TB7) on only one of the out-
door units.
6)
A transmission booster must be connected to a system in which
the total number of connected indoor units exceeds 20.
7)
A transmission booster is required in a system to which more
than 16 indoor including one or more indoor units of the 200
model or above are connected.
Refer to the DATABOOK for further information about how
many booster units are required for a given system.
8)
When a power supply unit is connected to the transmission line
BS_02_E
L11
Move the male connector
from CN41 to CN40.
SW5-1 OFF ON
Group
OC
IC
51
01
TB3
TB5
TB15
M1 M2
M1 M2
S
1 2
TB7
M1 M2
S
A B
To be connected
101
RC
L21
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
ON
Group
OC
54
TB3
M1 M2
M1 M2
TB7
M1 M2
S
To be left
unconnected
A B
A B
154
104
RC
Note1
System controller
A B S
Interlock operation with
the ventilation unit
L12
Group
Group
IC
02
TB5
TB15
TB5
M1 M2
M1 M2
S
1 2
A B
A B
102
103
RC
RC
L22
Group
IC
IC
IC
04
05
06
TB5
TB5
TB15
TB5
TB15
M1 M2
M1 M2
S
1 2
S
1 2
S
A B
106
RC
RC
Note1 When only the LM adapter is connected,
leave SW5-1 to OFF (as it is).
Note2 LM adapters require the power supply
capacity of single-phase AC 220/240V.
for centralized control, leave the power jumper connector on
CN41 as it is (factory setting).
(3) Maximum allowable length
1)
Indoor/outdoor transmission line
Same as 2-7-3
2)
Transmission line for centralized control
Same as 2-7-4
3)
M-NET remote controller wiring
Maximum overall line length
2
(0.3 to 1.25mm
[AWG22 to 16])
m1
10m [32ft]
m2+m3
10m [32ft]
If the standard-supplied cable must be extended, use a cable
with a diameter of 1.25mm
that exceeds 10m [32ft] must be included in the maximum in-
door-outdoor transmission line distance described in 1).
*When connected to the terminal block on the Simple remote
controller, use cables that meet the following cable size specifi-
cations: 0.75 - 1.25 mm
4)
Maximum line distance via outdoor unit
2
(1.25 mm
[AWG16] min.)
Same as 2-7-4
LC
IC
03
07
TB15
TB5
M1 M2
S
1 2
S
LC
08
TB15
TB5
M1 M2
1 2
S
2
[AWG16]. The section of the cable
2
[AWG18-14].
21
chapter 2 -