[8-15 Main-HBC Maintenance Instructions ]
Operation procedures
13) To flatten the motor, insert the fixed piece into the central hole of the
motor air hood to lock the horizontal groove at the end of the motor
shaft, and use the torque wrench S13 to screw the nylon lock nut (part
20).
<<Note>>
Tightening torque: 11-13 N·m
14) Erect the motor and mount the sealing gasket (part 17) on the guide
vane (part 12) stop.
<<Note>>
Gasket light face down.
15) Install them into the water inlet body (part 1).
<<Note>>
The plug hole on the side alings with the water outlet hole on the water out-
let body (part 7).
16) Install four pull rods (part 11), screw the pull rod into the threaded
hole of the motor (part 32). Install the spring washer (part 24), and
tighten the hexagonal (part 25).
BS_08_L
Illustrations
Seal gasket
Air-discharge hole
Water Inlet
body
Spring washer
chapter 8 -