[8-13 Parts Replacement Instructions (Outdoor Unit) ]
(10) Remove the braze at the two areas circled in Figure 10 to remove SV2 assembly. (See Figure 10.)
Remove the
braze here.
(11) Cut the pipe with a pipe cutter at the area shown in Figure 11.
Remove the braze at the area circled in Figure 11 to remove LEV4 assembly. (See Figure 11.)
Figure 11
BS_08_L
SV2
Figure 10
Remove the
braze here.
Injection pipe
LEV4
Cut the
pipe here.
Rubber spacer
Remove the braze here.
SV2
SV2 assembly
Injection pipe
LEV4
Cut the
pipe here.
Leave the rubber
spacer attached.
LEV4 assembly
Remove the braze here.
The replacement parts for
this part is included with the
replacement kit that contains
check valve block assembly.
Use the pipe included with
the check valve.