Download Print this page

Error Code [7130] - Mitsubishi Electric PURY-M200YNW-A1 Service Handbook

Hide thumbs Also See for PURY-M200YNW-A1:

Advertisement

[7-9 Error Code Definitions and Solutions: Codes [7000 - 7999] ]
7-9-7
Error Code [7113]
1. Error code definition
Function setting error (improper connection of CNTYP)
2. Error source, cause, check method and remedy
After troubleshooting the error using the check methods and remedies shown below, turn the power back on.
Error source
Outdoor unit
(1)
Wiring fault
(2)
Loose connectors, short-cir-
cuit, contact failure
(3)
Incompatible control board
and INV board (replacement
with a wrong circuit board)
(4)
DIP SW setting error on the
control board
HBC
(1)
Wiring fault
(2)
Loose connectors, short-cir-
cuit, contact failure
BS_07_M
Cause
(Detail code 15)
1) Check the connector CNTYP5 on the control board for proper con-
nection.
2) Check the connector CNTYP4 on the control board for proper con-
nection.
(Detail code 14)
1) Check the connector CNTYP4 on the control board for proper con-
nection.
2) Check the settings of SW5-3 through SW5-6 on the control board.
(Detail code 12)
1) Check the connector CNTYP2 on the control board for proper con-
nection.
2) Check the connector CNTYP5 on the control board for proper con-
nection.
3) Check the settings of SW5-3 through SW5-6 on the control board.
(Detail code 16)
1) Check the connector CNTYP on the INV board for proper connec-
tion.
2) Check the connector CNTYP5 on the control board for proper con-
nection.
3) Check the settings of SW5-3 through SW5-6 on the control board.
4) Check the wiring between the control board and INV board.
Refer to the following page(s). [7-2-1 Error Code [0403]]
(Detail code 0, 1, 5)
1) Check the wiring between the control board and INV board.
Refer to the following page(s). [7-2-1 Error Code [0403]]
2) Check the settings of SW5-3 through SW5-6 on the control board.
3) Check the connector CNTYP5 on the control board for proper con-
nection.
(Detail code 1)
1) Check the connector CN409 on the control board for proper con-
nection.
(Detail code 2)
1) Check the connector CN410 on the control board for proper con-
nection.
(Detail code 82)
1) Check the wiring between the control board and the PS board.
Refer to the following page(s). [7-2-1 Error Code [0403]]
2) Check the power-supply voltage and the frequency.
Refer to the following page(s). [7-6-5 Error Code [4115] Detail
Code 101, 102]
3) Replace the power-supply board.
Check method and remedy