Download Print this page

Mitsubishi Electric PURY-M200YNW-A1 Service Handbook page 379

Hide thumbs Also See for PURY-M200YNW-A1:

Advertisement

[8-13 Parts Replacement Instructions (Outdoor Unit) ]
2. L-module
Rear heat exchanger
Front of the unit
Figure 1
(1) Remove the two front panels from the unit by unscrewing the 14 screws. (See Figure 2.)
(2) Remove the fin guard by unscrewing the 12 screws. (See Figure 2.)
(3) Remove the cable straps holding the weak and strong electrical wirings. (See Figure 3.)
(4) Remove the center pillar by unscrewing the 5 screws. (See Figure 2.)
(5) Remove the drain cover by unscrewing the screw and cutting the cable tie. (See Figures 3 and 4.)
When re-placing the drain pan cover, make sure that the silicon tube is properly placed on the defrost pipe, and then fix the
drain pan cover in place with a cable tie.
(6) Remove the drain pan by unscrewing the 2 screws. (See Figure 3.)
Be sure to remove the two rod holders holding the check joints to the drain pan. (See Figure 4.)
Fin guard
Center pillar
Figure 2
(7) Remove the cover from the control box by unscrewing the 5 screws. (See Figure 5.)
(8) Remove the cable straps holding motor wiring. (See Figure 6.)
Control box cover
Figure 5
112
- chapter 8
Front heat exchanger
Cable strap for
holding strong
Drain pan cover
electrical wiring
Drain pan
Figure 3
Cable strap for
holding weak
electrical wiring
Drain pan cover
Rod holder
Figure 4
Cable strap
Figure 6
Defrost pipe
Silicon tube
BS_08_L

Hide quick links:

Advertisement

loading