[8-5 Pressure Sensor Circuit Configuration and Troubleshooting Pressure Sensor Problems ]

8-5
Pressure Sensor Circuit Configuration and Troubleshooting
Pressure Sensor Problems
8-5-1

Comparing the High-Pressure Sensor Measurement and Gauge Pressure

Setting the digital display switch (SW4 (SW6-10: OFF) as follows will display the high-pressure sensor reading on the service
LED (LED301) on the control board.
ON
1
2
3
4
5
6
7
8
9 10
(1) While the sensor is stopped, compare the gauge pressure and the pressure displayed on the
self-diagnosis service LED.
1) When the gauge pressure is between 0 and 0.098MPa [14psi], internal pressure is caused due to gas leak.
2) When the pressure displayed on the self-diagnosis service LED is between 0 and 0.098MPa [14psi], the connector may be
defective or be disconnected. Check the connector and go to (4).
3) When the pressure displayed on the self-diagnosis service LED exceeds 4.15MPa [601psi], go to (3).
4) If other than 1), 2) or 3), compare the pressures while the sensor is running. Go to (2).
(2) Compare the gauge pressure and the pressure displayed on the self-diagnosis service LED
while the sensor is running. (Compare them by MPa [psi] unit.)
1) When the difference between both pressures is within 0.098MPa [14psi], both the high pressure sensor and the control board
are normal.
2) When the difference between both pressures exceeds 0.098MPa [14psi], the high pressure sensor has a problem. (perfor-
mance deterioration)
3) When the pressure displayed on the self-diagnosis service LED does not change, the high pressure sensor has a problem.
(3) Remove the high pressure sensor from the control board to check the pressure on the self-di-
agnosis service LED.
1) When the pressure displayed on the self-diagnosis service LED is between 0 and 0.098MPa [14psi], the high pressure sensor
has a problem.
2) When the pressure displayed on the self-diagnosis service LED is approximately 4.15MPa [601psi], the control board has a
problem.
(4) Remove the high pressure sensor from the control board, and short-circuit between the No.2
and 3 connectors (63HS1, PS1, PS3) to check the pressure with the self-diagnosis service LED.
1) When the pressure displayed on the self-diagnosis service LED exceeds 4.15MPa [601psi], the high pressure sensor has a
problem.
2) If other than 1), the control board has a problem.
18
- chapter 8
SW4
ON
1
2
The figure at left shows that the switches 1 through 5 are set to ON and 6 through 10 are set to OFF.
3
4
5
6
7
8
9 10
BS_08_L