System With A Connection Of System Controller To Centralized Control Transmission Line - Mitsubishi Electric PUHY-HP200YNW-A Service Handbook

Advertisement

[2-7 Example System with an MA Remote Controller ]
2-7-4
System with a Connection of System Controller to Centralized Control
Transmission Line
(1) Sample control wiring
An example of a system in which a system controller is connected to the transmission cable for the centralized control system
and the power is supplied from the outdoor unit
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
ON
OS2
53
TB3
M1 M2
TB7
M1 M2
S
To be left
unconnected
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
ON
OS2
56
TB3
M1 M2
TB7
M1 M2
S
To be left
unconnected
(2) Cautions
1)
ME remote controller and MA remote controller cannot both be
connected to the same group of indoor units.
2)
No more than 2 MA remote controllers can be connected to a
group of indoor units.
3)
Do not connect the terminal blocks (TB5) on the indoor units that
are connected to different outdoor units with each other.
4)
Replacement of male power jumper connector (CN41) must be
performed only on one of the outdoor units (not required if power
to the transmission line for centralized control is supplied from a
controller with a power supply function, such as GB-50ADA).
5)
Short-circuit the shield terminal (S terminal) and the earth termi-
nal (
) on the terminal block for transmission line for central-
ized control (TB7) on the outdoor unit whose power jumper
connector is mated with CN40.
6)
A transmission booster is required in a system to which more
than 32 indoor units (26 units if one or more indoor units of the
200 model or above is connected) are connected.
Refer to the DATABOOK for further information about how
many booster units are required for a given system.
7)
When a power supply unit is connected to the transmission line
18
- chapter 2
L11
Move the male connector
Leave the male
from CN41 to CN40.
connector on
CN41 as it is.
SW5-1 OFF ON
SW5-1 OFF
ON
OS1
OC
52
51
TB3
TB3
M1 M2
M1 M2
TB7
TB7
M1 M2
S
M1 M2
S
To be left
unconnected
To be connected
L21
Leave the male
Leave the male
connector on
connector on
CN41 as it is.
CN41 as it is.
SW5-1 OFF
ON
SW5-1 OFF
ON
OS1
OC
55
54
TB3
TB3
M1 M2
M1 M2
TB7
TB7
M1 M2
S
M1 M2
S
To be left
unconnected
To be left
unconnected
System controller
A B S
L12
Group
Group
IC
IC
01
02
TB5
TB15
TB5
TB15
M1 M2
S
1 2
M1 M2
S
1 2
A B
A B
MA
MA
L22
Group
IC
IC
04
05
TB5
TB5
TB15
TB15
M1 M2
S
1 2
M1 M2
S
1 2
A B
MA
m3
Note1 When only the LM adapter is connected,
leave SW5-1 to OFF (as it is).
Note2 LM adapters require the power supply
Note1
capacity of single-phase AC 220/240V.
for centralized control, leave the power jumper connector on
CN41 as it is (factory setting).
(3) Maximum allowable length
1)
Indoor/outdoor transmission line
Same as 2-7-3
2) Transmission line for centralized control
L31+L32(L21)
3)
MA remote controller wiring
Same as 2-7-1
4)
Maximum line distance via outdoor unit
2
(1.25mm
[AWG16] or larger)
L32+L31+L12(L11)
L32+L22(L21)
L12(L11)+L31+L22(L21)
*1 If a given system includes one or more unit or remote control-
ler that does not support the maximum allowable cable dis-
tance of 1,000 m [3280 ft], the maximum allowable cable
distance in the system will be 500 m [1640 ft]. Refer to the lat-
est catalog for information on which units and remote control-
lers support the maximum allowable cable distance of 1,000
m [3280 ft].
Interlock operation with
the ventilation unit
Group
LC
IC
03
07
TB5
TB15
TB5
M1 M2
S
1 2
M1 M2
S
A B
MA
Group
LC
IC
06
08
TB5
TB15
TB5
M1 M2
M1 M2
S
S
1 2
A B
MA
200m [656ft]
1000 m [3280ft] (500 m [1640ft])
1000 m [3280ft] (500 m [1640ft])
1000 m [3280ft] (500 m [1640ft])
*1
*1
*1
BS_02_M

Advertisement

loading

This manual is also suitable for:

Puhy-hp250ynw-aPuhy-hp400ysnw-aPuhy-hp500ysnw-a