6 Related Drive Parameters

BACnet Node Addressing

You can use F6-45 to set the BACnet node address. This defines the physical address of
the drive on the MS/TP network. You can also set the Device Object Instance Identifier
[F6-48 and F6-49] and the Device Object Name (via BACnet network). These allow the
drive to have a virtual address and simplify the controller configuration.
After you set the addresses, a controller can initiate communication to the drive. The drive
will do the specified function and send a response back to the controller. The drive will
usually respond immediately, but the drive can delay its response until it gets the token for
commands that may take extra local processing time.
Electronic Protocol Implementation Conformance Statement (EPICS)
Files
For easy network implementation of drives equipped with the SI-B3 option, you can get
an EPICS file from:
U.S.: https://www.yaskawa.com
Other areas: Contact a Yaskawa representative.
Refer to
BACnet Protocol Implementation Conformance Statement on page 56
B3 PICS.
6
Related Drive Parameters
These parameters set the drive for operation with the option. Make sure that the parameter
settings in this table are correct before you start network communications.
Note:
Hex.: MEMOBUS addresses that you can use to change parameters over network communication are
represented in hexadecimal numbers.
32
YASKAWA TOEP YAICOM 22A BACnet MS/TP Installation & Technical Manual