Advertisement

Section 5: Customizing Actuator Settings
February 2018
Figure 5-13
Analog Setup
NOTE: The actuator senses that the Futronic ACM is installed and adjusts the display sequence to display
only one input.
Go to Figure 5-13
BACK
Bandwidth =
<0.1-5.0% in 0.1%
ANALOG
increments>
YES
SETUP?
YES
NO
OR
NEXT
Go to next display
Bandwidth =
See Figure 5-4
<0.5-9.0% in 0.5%
increments>
YES
Delay Time =
<xx.xx> SEC
<0-60 sec in 1 sec
increments>
YES
Polarity Close =
<4/20>mA
YES
Polarity Close =
<4/20>mA
YES
<LostSigAction>
NO
Stayput or
Go To Position
YES
Go to Position on
Lost Signal?
YES
Go to <xx%>
<0-100% in 1%
increments>
60
All manuals and user guides at all-guides.com

Figure 5-13 Analog Setup

Position
Control Mode Analog?
<x.x>%
Speed
ACM Installed?
<x.x>%
NO
NO
Input
NO
Output
NO
On Lost
Signal?
NO
on Lost
Signal?
YES
Installation and Operation Manual
Analog Input #1
NO
<on/off>
YES
Analog
Control
YES
<ain1/ain2>
YES
NO
Analog Control AIN 1?
YES
Analog
Input #2
Alarm
<on/off>
YES
AO #1 Source
<position, setpoint,
torque, network>
YES
AO #2 Source
<position, setpoint,
torque, network>
YES
Go to Figure 5-13-1
E2K-405-0218 Rev. 2
Alarm
YES
Control Mode Analog?
YES
NO
NO
ACM Installed?
YES
Customizing Actuator Settings