5.5.8

Analog Setup (ACM Required)

NOTE:
Only displayed/applicable if the ACM is installed and analog control is enabled in
the valve control setup. See Section 5.5.2, Valve Control Setup.
All analog I/O are loop powered.
1.
2.
3.
4.
To calibrate analog input, connect a calibrated precision 4-20mA current source to
Terminal 25(+) and 26(-) for AIN#1.
To calibrate analog input AIN#2, connect a calibrated precision 4-20mA current
source to Terminal 27(+) and 28(-).
To calibrate analog outputs, the user must connect a calibrated precision
4-20mA current meter to Terminals 31(+) and 32(-) for AO#1 or Terminals 29(+)
and 30(-) for AO#2.
To calibrate analog output AO#2, the user must connect a calibrated precision
4-20mA current meter to terminals to 33(+) and 34(-).
Customizing Actuator Settings
All manuals and user guides at all-guides.com
At the "ANALOG SETUP?" prompt, answer "YES."
Use the selector knob (NEXT/BACK) to review the settings for
analog control.
Use the control knob (NO) to increment the bandwidths and delay
time, to select polarity and lost signal parameters, and to calibrate
analog in/out.
Answer "YES" after each selection. See Figure 5-13.
Section 5: Customizing Actuator Settings