Two-Wire Control
The two-wire control mode uses only one contact to control the valve. When the contact
is closed, the valve opens, and when the contact is open, the valve closes. The contact
open and close status can be reversed in the "SETUP" mode. See Section 5.5.4, Discrete
Input Setup.
Three-Wire Control
The three-wire control mode uses two maintained contacts to open or close the valve.
This is an "inching" type mode. Remote seal-ins, "Momentary" mode, may be activated in
the "SETUP" mode. If the three-wire control is used with the seal-ins activated, the valve
cannot be stopped while being remotely controlled; the valve can only be stopped via the
inhibit or emergency stop inputs.
Four-Wire Control
The four-wire control mode uses three maintained contacts to open, close, or stop the
valve. The default configuration sets the stop input to be active on open contact.
The default configuration can be modified in the "SETUP" mode. See Section 5.5.4,
Discrete Input Setup.