Figure 5-13-3 Analog Output 1 Calibration Setup - Emerson Bettis TEC2 Installation And Operation Manual

With model 500
Hide thumbs Also See for Bettis TEC2:
Table of Contents

Advertisement

Installation and Operation Manual
E2K-405-0218 Rev. 2
Figure 5-13-3
Analog Output 1 Calibration Setup
Calibrate
AO#1
4-20MA?
NO
Customizing Actuator Settings
All manuals and user guides at all-guides.com
Figure 5-13-3 Analog Output 1
Calibration Setup
NO
YES
Calibrate
Is External Meter
YES
4MA?
Connected?
NO
Increase Value
0.01 mA
Decrease Value
0.01 mA
Calibrate
Is External Meter
20MA?
Connected?
YES
NO
Increase Value
0.01 mA
Decrease Value
0.01 mA
Section 5: Customizing Actuator Settings
Go to
Figure 5-13-2
Accept 4MA
YES
Setting?
NO
YES
NEXT
Increase Setting
0.01MA?
NO
NO
OR
YES
NEXT
Decrease Setting
0.01MA?
YES
Accept 20MA
Setting?
YES
NO
YES
NEXT
Increase Setting
0.01MA?
NO
NO
OR
YES
NEXT
Decrease Setting
0.01MA?
YES
February 2018
63