Section 3: Installation
February 2018
Figure 3-22
TEC2 Wiring Diagram
Motor
Thermal
Motor
Protector
Control
Module
Local Display Module
Two-Wire Control
Three-Wire Control
Maintain Contact to Open
Maintained Contacts
Open
Open
1
1
Close
4
Internal
2
0V
Power
10
Supply
4
+24 VDC
9
0V
10
+24 VDC
9
Open
1
1
+
External
Power
-
4
2
Supply
Common 0V
18-150 VDC
or
20-250 VAC
4
Common 0V
NOTES:
1) All digital inputs have an input votage range or 18-150 VDC or 20-250 VAC.
2) All digital relay outputs are rated for 5A @ 30 VDC or 5A @ 250 VAC Resistive, 2A inductive load.
3) Jumpers shown connected between terminals are permissible but not required.
4) Emergency stop requires jumper or normally closed contact (actuator stops when contact open)
5) Remote display communication port is RS-485.
6) If bare wires (without terminals) are connected, remove a maximum of .25 inch insulation.
7) User replaceable primary fuses (F1 and F2) are located in the Terminal Chamber Enclosure.
All transformer secondary fuses are automatic resetting.
8) Contacts Outputs and Output Switch Contact Development Chart shown for default configuration only.
User may redefine all Outputs (See TEC200O Installation & Operation Manual E2K-405-0902).
NOTE:
The Local Display Module (LDM) is a part of the actuator and is powered internally by a low voltage DC.
The Remote Display Module (RDM) is powered by two options, either 24VDC or 90-250VAC 50/60Hz.
28
All manuals and user guides at all-guides.com
24 VDC
Power
Supply
Central Control Module
Note: Maximum Power Rating: 15.12 Watts
Maximum Source Current: 0.63 Amps
Remote Display Module
(1 or 2 May be fitted)
Four-Wire Contol
Inhibit/Interlock
Momentary Contacts
Open
1
5
Close
2
6
Stop
3
7
4
8
0V
10
10
+24 VDC
9
9
Open
Open
1
5
Close
Close
2
6
+
-
Stop
3
7
+
-
Common 0V
4
8
Installation and Operation Manual
R0#1
R0#2
R0#3
and ESD
R0#4
Open Inhibit
Monitor
Relay
Close Inhibit
R0#5
ESD
0V
Separate
+24 VDC
Terminal
Chamber
Open Inhibit
Close Inhibit
ESD
+
-
Common 0V
LSO
LSC
LSA
LSB
DWN BY JTD
WIRING
DIAGRAM
E2K-405-0218 Rev. 2
L1
3 - Phase
L2
Power
L3
Supply
GND
1
Open
2
Close
3
Stop
4
Common 0V
5
Open Inhibit
6
Close Inihbit
7
ESD
8
Common 0V
9
+24 VDC
10
0 VDC
11
LSO
12
Common
13
LSC
14
LSA
15
Common
16
LSB
17
N.O. Contact
18
Common
19
N.C. Contact
Emergency
20
Stop
21
RS485 (+)
Emergency
22
Stop
23
RS485 (-)
24
Shield
36
DCMlink
TM
38
Output Switch Contact Development
Valve Position
Contact
Function
MID
Close
Open
Open Limit
Close Limit
Open Limit
Close Limit
ORIGINAL DATE 4-21-03
TEC-001
Installation