Sealing Cable/Conduit Entries; Recommended Terminal Connections - Emerson Bettis TEC2 Installation And Operation Manual

With model 500
Hide thumbs Also See for Bettis TEC2:
Table of Contents

Advertisement

Section 3: Installation
February 2018
3.3.2

Sealing Cable/Conduit Entries

Seal the cable and conduit entries in accordance with the National Electric Code
or your country standard and applicable local codes. All conduit entries should be
sealed against the site environment. All unused conduit entries must be sealed
with threaded metal plugs.
3.3.3

Recommended Terminal Connections

The TEC2 terminal block connectors are wire binding screw connectors with rising
captive plates. Connections can be made one of three ways:
1.
2.
3.
Figure 3-3 details power terminal size and length of bare wire strip. Figure 3-4
details control terminal size and length of bare wire strip.
12
All manuals and user guides at all-guides.com
Strip and connect bare wire.
Strip and install wire ferrule.
Strip and install crimp-on insulated or non-insulated ring or fork-tongue
connectors for either M3 control signal terminal block screws or M4 power
terminal screws.
Loosen terminal block connectors L1, L2, L3 and GND screws with a
common or Phillips head screwdriver.
If bare wire is being used, strip insulation a maximum of 0.4 inch (10 mm).
Insert wire or wire lug under terminal block connector screw clamps
and tighten.
Installation and Operation Manual
E2K-405-0218 Rev. 2
Installation