Table 4-4 Default Configuration Settings - Emerson Bettis TEC2 Installation And Operation Manual

With model 500
Hide thumbs Also See for Bettis TEC2:
Table of Contents

Advertisement

Section 4: Operation
February 2018
Table 4-4.
Basic Actuator Functions
Valve
Control
Mode = 3 Wire
Close Direction
= (Gearing
Dependent)
Seat = Position
Close Torque = 50%
Open Torque = 50%
Local Control =
Maintain
Remote Control =
Maintain
Torque Retry = OFF
Remote Display 1
= OFF
Remote Display 2
= OFF
Close LED = Green
Open LED = Red
Low Battery Alarm
= OFF
Valve Stall Delay
Time = 8 Sec
Retain Setpoint =
OFF
* Overriding the thermal motor protection will invalidate the hazardous area certification.
34
All manuals and user guides at all-guides.com
Default Configuration Settings
Discrete
(Relays
Inputs
1 thru 5)
DI#1= Active on
RO#1= LSO
CLOSED contact
DI#2= Active on
RO#1= N.O.
CLOSED contact
DI#3= Active on
RO#1= Continuous RO#9 = Flash
OPEN contact
DI#4= Active on
RO#2= LSC
CLOSED contact
DI#5= Active on
RO#2= N.O.
CLOSED contact
DI#6= Active on
RO#2= Continuous RO#10 = Flash
OPEN contact
RO#3= LSO
RO#3= N.O.
RO#3= Continuous RO#11 = Flash
RO#4= LSC
RO#4= N.O.
RO#4= Continuous RO#12 = Flash
RO#5= MONITOR
RO#5= Continuous
LSA Position = 25%
LSB Position = 75%
Installation and Operation Manual
Discrete Outputs
(ARM Relays
9 thru 12)
RO#9 = Lost Power
Open Inhibit = OFF
Alarm
RO#9 = N.O.
Close Inhibit = OFF
Local ESD = OFF
RO#10 = Motor
Remote ESD = OFF
Overload Alarm
Lost Com ESD =
RO#10 = N.O.
OFF
Stayput on ESD =
ON
RO#11 = Lost
*ESD Override on
Phase Alarm
Thermal = OFF
ESD Override on
RO#11 = N.O.
Local = OFF
ESD Override on
Stop = OFF
RO#12 = Over
ESD Override on
Torque Alarm
Inhibit = OFF
ESD Override on
RO#12 = N.O.
Torque = OFF
ESD Delay 0.0
Seconds
Go to _% Open on
ESD = 0
E2K-405-0218 Rev. 2
Inhibit and ESD
Operation