Section 5: Customizing Actuator Settings
February 2018
5.5.3
Set Valve Travel Limits
1.
2.
See Figures 5-7 and 5-8.
Figure 5-7
Set Valve Travel Limits
Figure 5-7 Normal Operation Mode - Set Limits With Electrical Operation
Normal Operation Mode - Set Limits with Electrical Operation
Go to
Figure 5-6
BACK
SET VALVE
TRAVEL LIMITS?
NO
Go to
Figure 5-4
50
All manuals and user guides at all-guides.com
If the close limit is acceptable, answer "YES." If not rotate the selector
knob to LOCAL. Close valve to desired limit, rotate selector knob to STOP,
and answer YES.
If the open limit is acceptable, answer "YES." If not rotate the selector
knob to LOCAL. Open valve to desired limit, rotate selector knob to STOP,
and answer YES.
BACK
Accept Valve
Close Limit?
YES
NO
Select Local
and
Close Valve
STOP
LOCAL
Close Valve
Then
Select Stop
Use control knob to move
valve in "CLOSE" direction.
When done, select "STOP".
YES
SAVE LIMITS?
NO
Installation and Operation Manual
NEXT
Accept Valve
Open Limit?
YES
NO
Select Local
and
Open Valve
STOP
LOCAL
Open Valve
Then
Select Stop
Use control knob to move
valve in "OPEN" direction.
When done, select "STOP".
Customizing Actuator Settings
E2K-405-0218 Rev. 2
YES