Installation and Operation Manual
E2K-405-0218 Rev. 2
Two-Speed Timer Default Configuration
Close
Mode = OFF
Start Position = 30%
Stop Position = 1%
Pulse ON time = 3.5 Sec
Pulse OFF time = 5.0 Sec
Auxiliary Control Module (ACM) Default Configuration
Analog Control - Futronic
Control Bandwidth = 2.0%
Speed Bandwidth = 5.0%
Delay Time = 1 Second
Input Polarity CLOSE = 4mA
Output Polarity CLOSE = 4mA
STAYPUT on lost signal
1.
2.
3.
4.
NOTE:
The "DISPLAY SETTINGS?" mode can be accessed without entering a passcode;
however no changes can be made to the settings in this mode. To make any
changes see Section 5, Customizing Actuator Settings.
Operation
All manuals and user guides at all-guides.com
Open
Mode = OFF
Start Position = 70%
Stop Position = 99%
Pulse ON time = 3.5 Sec
Pulse OFF time = 5.0 Sec
Enter "SETUP" mode as detailed in Step No 2 of Section 2, Quick Start.
Place the selector knob in the NEXT position to advance through each
display until "DISPLAY SETTINGS?" is displayed.
Rotate the control knob to YES.
Scan through each display selecting NO or YES and BACK or NEXT as
needed to review the current settings. See Figure 4-4.
Section 4: Operation
Anti-Water Hammer
Mode = OFF
Start Position = 10%
Pulse ON time = 3.5 Sec
Pulse OFF time = 5.0 Sec
Network Control - Controlinc
Network Node Address = 001
Response Delay Time = 8ms
Parity = NONE
Analog I/0 Scale 0 - 4095
Write Protect = NO
February 2018