Section 3: Installation
February 2018
Figure 3-10
Alternate
Default
Function
Function
Open
Close
Stop
Common (0V) for Control Inputs (1-3)
Open Inhibit
Close Inhibit
ESD
Common (0V) for Inhibit/ESD Inputs (4-6)
User Power Supply
24VDC Power Supply
Relay Output #1
Limit Switch Open (LSO)
Relay Output #2
Limit Switch Close (LSC)
Relay Output #3
Intermediate Limit A (LSA)
Relay Output #4
Intermediate Limit B (LSB)
Relay Output #5
Emergency Stop (N.C.)
Remote Display Model Communication Port (+)
Emergency Stop (N.C.)
Remote Display Model Communication Port (-)
Notes:
1.
2.
3.
4.
5.
6.
Figure 3-11
18
All manuals and user guides at all-guides.com
ACM Installation Connections - ACM
(Network Control Module)
Signal
Digital Input #1
Digital Input #2
Digital Input #3
Digital Input #4
Digital Input #5
Digital Input #6
}
(+)
(-)
}
}
}
}
}
Monitor Relay N.O.
}
Monitor Relay N.C.
Earth Ground
All digital inputs have an input voltage range of 18-150 Vdc or 20-250 Vac.
All digital relay outputs are rated for 5 A @ 30 Vdc or 5 A @ 250 Vac
Resistive, 2 A Inductive load.
Jumpers can be added between Terminals 8 and 10, Terminals 32 and 34,
Terminals 36 and 38, and Terminals 40 and 42 but are not required.
Emergency Stop requires jumper (between Terminals 20 and 22) or
normally closed contacts (actuator stops when contacts open).
Remote display communication port is RS-485.
If bare wires (without terminals) are connected, remove a maximum of
1/4 inch (6 mm) insulation.
ACM Wiring Connections
Installation and Operation Manual
E2K-405-0218 Rev. 2
AIN1+
AIN1-
AIN2+
ACM Option
AIN2-
Shield
All Analog I/O are Isolated,
Shield
Loop Powered
AO1+
with Channel to Channel Isolation
AO1-
AO2+
AO2-
Spare (n/c)
DCMlink (+)
Spare (n/c)
DCMlink (-)
(+)
}
Shield
Network Port A
(-)
CAM Option
}
Shield
(+)
Network Port B
(-)
ACM_CAM Option
ACM Wiring
Terminals
25 to 44
Installation