Eaton 93PR Series Installation And Operation Manual

Eaton 93PR Series Installation And Operation Manual

Table of Contents

Advertisement

Quick Links

Eaton
®
93PR UPS
15-80 kW
Installation and Operation Manual

Advertisement

Table of Contents
loading

Summary of Contents for Eaton 93PR Series

  • Page 1 Eaton ® 93PR UPS 15-80 kW Installation and Operation Manual...
  • Page 3 Please adhere to the warnings and instructions specified in the manual and on the equipment, and keep the manual properly for future reference. Do not try to operate the equipment before reading all the safety information and operation instructions The manual applies to the 93PR series, including: 93PR-15kVA 93PR-20kVA...
  • Page 4 The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts) without the written approval of Eaton Corporation. Every care has been taken to ensure the accuracy of the information contained in this manual, but no liability can be accepted for any errors or omission. The right to make design...
  • Page 5 一旦您使用产品软件,即表示您同意本协议的条款。 您使用产品软件的权利明确以您接受本协议为前提条件。 INFORMATION ABOUT US 关于我们的信息 1.1 EATON POWER QUALITY (SHANGHAI) CO., LTD. is registered in PRC and has its registered address at [B5, No. 76, Ribin Road, China (Shanghai) Pilot Free Trade Zone] (the “Contracting Entity”). 伊顿电源(上海)有限公司在中国注册(公司注册号[310115400090977]) ,其注册地址为[中国(上海)自由贸易试验区日滨 路76号B5部位](“缔约主体”)。...
  • Page 6 Product Software solely for your own internal business purposes; 指仅为您自身内部业务之目的,产品软件附带的或与产品软件一起提供的任何教程、用户指南和其他文 “文件” 件; “Eaton Hardware” means the Eaton product provided by Eaton to you, which may include Product Software within it; “伊顿硬件” 指由伊顿提供给您的伊顿产品,其中可能包括产品软件; “Eaton Open Source has the meaning as defined in Clause 10.1;...
  • Page 7 GRANT AND SCOPE OF LICENSE 许可的授予与范围 In consideration of you agreeing to abide by the terms of this Agreement, Eaton hereby grants to you, a limited, non-exclusive, non-transferable, non-sub-licensable, and revocable license to access and use the Product Software with the Eaton Hardware, which is provided to you for your own internal business purposes, solely for your use as permitted in these terms.
  • Page 8 和国际法律,包括与网络安全和盗版、数据保护、隐私、国际通信和技术或个人数据的传输有关的法律。 Eaton may make services available to you that are provided, in whole or in part, by other parties. Although Eaton may offer this opportunity, you acknowledge that any third party services that you use in connection with the Product Software are not part of the Product Software.
  • Page 9 必要设备 Full use of the Product Software is dependent upon your use of a device with Internet access and the purchase of Eaton Hardware in which it is installed or to which the Product Software pertains as described in the Documentation.
  • Page 10 司,复制、分发或以其他方式转让产品软件。 You may transfer the Product Software directly to a third party only in connection with the sale of the Eaton product in which it is installed or to which the Product Software pertains as described by Eaton in the Documentation. In the event of such a sale, you may not keep any copies of the Product Software or any portion thereof and you undertake to ensure the third party to whom you transfer the Product Software is made aware of, agrees to and complies with all of the provisions of this Agreement.
  • Page 11 Product Software in any way that is unlawful, fraudulent or deceptive, or has any unlawful, fraudulent or deceptive purpose or effect; 不以任何非法的、欺诈性的或欺骗性的方式使用产品软件,或具有任何非法的、欺诈性的或欺骗性的目的或效果; not use the Product Software except in conjunction with the operation of Eaton products to which the Product Software pertains or other products described by Eaton in the Documentation; 不使用该产品软件,除非与该产品软件相关的伊顿产品或伊顿在文件中描述的其他产品的操作相结合;...
  • Page 12 Eaton. Eaton shall not be liable for any costs, expenses or liabilities resulting from your failure to cooperate or to provide such information;...
  • Page 13 Third Party Licensor components or additional obligations by such Third Party Licensors that are not set forth in this Agreement, the terms of the license arrangement between Eaton and any such Third Party Licensor or the corresponding open source license will prevail.
  • Page 14 11.1 Where applicable, Eaton may charge you fees for access to the Product Software, as provided in Appendix 2. You agree to pay all fees and charges, within the agreed upon billing period, including taxes, incurred through your account at the rates in effect...
  • Page 15 In no event shall Eaton nor any of its officers or other representatives be liable for any loss or damages...
  • Page 16 (whether arising out of liability under breach of contract, tort (including but not limited to negligence), misrepresentation, breach of statutory duty, breach of warranty or claims by third parties arising from any breach of this agreement) of Eaton or its...
  • Page 17 18.1 Eaton are not obligated to monitor the access or use of the Product Software, but Eaton reserves the right to do so for the purpose of operating the Product Software, to ensure compliance with these terms, and to comply with applicable law or other legal requirements.
  • Page 18 Agreement. You agree not to otherwise disclose such information to any third party without the prior written consent of Eaton. You shall be liable to Eaton for any breach of the confidentiality obligations in this Clause 20 of this Agreement by your employees.
  • Page 19 Except for personally identifiable information/personal data, the use and disclosure of which is addressed in the Privacy Statement for the Product Software, any and all information and content provided by you to Eaton is provided on a non- proprietary and non-confidential basis, regardless of whether the information or content is marked or otherwise identified as confidential or proprietary.
  • Page 20 Eaton reserves the right, in its sole discretion and without notice to you, to suspend, terminate, modify or delete an account or access to the Product Software or parts thereof, if you are, or Eaton reasonably suspects that you are, failing to comply with any of the provisions of this Agreement or for any actual or suspected illegal or improper use of the Product Software.
  • Page 21 (together, “Third Party Links and Ads”). Such Third Party Links and Ads are not under Eaton’s control. Eaton disclaims all liability and responsibility for any Third Party Links and Ads and you acknowledge and agree that Eaton is not responsible or liable for: (a) the availability or accuracy of such Third Party Links and Ads;...
  • Page 22 You acknowledge and agree that Eaton is not liable for any loss or damage which may be incurred as a result of the availability of those external sites or resources, or as a result of any reliance placed by you on the completeness, accuracy or existence of any advertising, products or other materials on, or available from, such web sites or resources.
  • Page 23 Eaton’s failure to enforce a term of this Agreement is not a waiver of its right to do so later. No failure or delay by Eaton or its affiliates to exercise any right or enforce any obligation shall impair or be construed as a waiver or ongoing waiver of that or any other right or power.
  • Page 24 27.3 Eaton may terminate this Agreement with thirty (30) days’ prior written notice if Eaton may not deliver or grant access to the Product Software, Documentation and Materials to you due to an embargo or other comparable trade sanction, which is expected to be in place for six (6) months or longer.
  • Page 25 This Agreement (and any associated order form or other agreements referenced herein) constitutes the entire and exclusive agreement between you and Eaton with respect to the subject matter of this Agreement, and supersedes and replaces any other prior or contemporaneous agreements, or terms and conditions applicable to the subject matter of this Agreement. No provisions in your purchase orders, or in any other business forms employed by you, will supersede the terms and conditions of this Agreement.
  • Page 26 31. CONTACT US 联系我们 Any questions regarding this Agreement should be directed to Eaton at: 关于本协议的任何问题,应向伊顿提出,地址是: Eaton 伊顿 Attn: IP Law Group 收件人:知识产权法组 1000 Eaton Boulevard 1000 Eaton Boulevard Mail Code 4N 邮件代码:4N Cleveland, OH 44122 Cleveland, OH 44122 Eaton 伊顿...
  • Page 27: Table Of Contents

    4.5. Wiring of the UPS Parallel System ........................39 4.5.1. Overview of power cables ........................39 4.5.2. Control signal overview ........................41 4.5.3. Installation of the parallel control wiring ....................41 Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 28 Regular maintenance .......................... 79 7.2.4. Annual maintenance ..........................79 7.2.5. Battery maintenance ..........................79 7.3. Installation of Battery ............................79 7.4. Maintenance Training ............................80 Chapter 8 Technical Indicators of Product ........................81 Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 29 Standard .............................. 81 8.2.2. UPS input ............................82 8.2.3. UPS output ............................82 8.2.4. Battery specifications ........................... 83 8.2.5. Environment ............................83 Chapter 9 WARRANTY ................................. 85 Chapter 10 INSTALLATION CHECKLIST ..........................86 Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 30 Figure 6-17: Clear Log interface ............................56 Figure 6-18: Info. interface 1 ..............................57 Figure 6-19: Info. interface 2 ..............................57 Figure 6-20: Password verification setting interface ......................58 Figure 6-21: Setting interface .............................. 58 Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 31 Figure 6-39: Switch status in Maintenance Bypass Mode ....................73 Figure 6-40: Switch status in online mode..........................73 Figure 7-1: Location of 15–40k air filter screen ........................76 Figure 7-2: Location of 60–80k air filter screen ........................76 Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 32 Table 8-1: Gas concentrations recommended in Table B1 of ANSI/ISA-71.04-2013 for G1 equipment environment ..84 Table 8-2: Requirements on the environment for transportation and storage within 1 year ..........84 Table 10-1: User Settings ..............................88 Table 10-2: Configuration Settings ............................88 Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 33: Chapter 1 Safety Instructions Tions

    3) Do not place tools or metal parts on top of batteries; 4) Wear a rubber jacket and a pair of rubber boots. • Electrical energy is dangerous. Do not attempt to alter any battery wiring or other connecting wiring, as this may result in injury. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 34 Make sure that the forklift fork is inserted into the forklift slot at the horizontal position. Do not tilt the fork upwards. • Insert the forks all the way through the base. Damage to the wiring channels and wiring may be caused by failure to comply with these instructions. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 35: Certification

    The product has received EMC Directive 2004/108/EC certification: UPS EN 62040-1 (Safety) and EN 62040-2(EMC) standard declaration can be obtained via the website (http://powerquality.eaton.com) or the local office of Eaton and licensed partners. 1.2. User Precautions The only user operations permitted are: •...
  • Page 36: Conventions Used In This Manual

    This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 37: Table 1-1: Acronyms And Abbreviations

    Emergency Power Off switch Maintenance Bypass Switch REPO Remote Emergency Power Off Advanced Battery Management HotSync HotSync wireless parallel technology Energy Saver System Input relay Battery relay Inverter relay Terminal block VRLA Valve-regulated lead-acid Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 38: Environment

    Obtaining information about regional service locations and their numbers. • For questions about anything in this manual. • For issues not covered in this manual. Please contact customer service via our 24-hour service hotline at 400-889-3938 Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 39: Chapter 2 Introduction

    Eaton has accumulated over the past five decades. It can fully meet the power supply security necessary for data centers, financial centers, enterprise computer rooms, industrial automation, education systems, medical systems, large offices and other application scenarios.
  • Page 40: Figure 2-2: Structure Of 15-40K Product

    Battery startup Mini-Slot card Power module Communication interface EMI board Input switch Bypass switch Terminal block Maintenance bypass switch Output switch Grounding screw Figure 2-2: Structure of 15-40k product Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 41: Figure 2-3: Structure Of 60-80K Product

    Installation and Operation Manual Battery startup Communication interface Power module Maintenance bypass switch Bypass switch Output switch Input switch Terminal block EMI board Grounding screw Figure 2-3: Structure of 60-80k product Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 42: Internal Structure Of Ups System

    AC power supply recovers. In the case of long-time interruption of power supply, the UPS will allow switching to another power system (e.g., generator) or shut down the loads in sequence. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 43: Operation Modes Of The Ups

    AC power is within the acceptable voltage and frequency range. Online Mode Figure 2-5 indicates the route that the electric energy runs through the UPS system in Online mode. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 44: Figure 2-5: Route Of The Electric Energy Running Through The Ups In Online Mode

    UPS turns normal. In an external parallel redundant system, each UPS can be isolated from the system to facilitate maintenance, while other UPSs continue to supply power to the load in Online mode. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 45: Figure 2-6: Route Of The Electric Energy Running Through The Ups In Ess Mode

    Within 20–100% of the rated load, the system efficiency is as high as 99% in ESS mode. Internal relay contacts Figure 2-6: Route of the electric energy running through the UPS in ESS mode Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 46: Battery Mode

    Whenever AC power recovers again during the battery discharge, K1 will be closed, and the UPS will return to online operation mode. The UPS will start charging the battery to recover its capacity. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 47: Bypass Mode

    The static bypass is composed of a SCR and a SSW. When the inverter cannot support the load, the static switch will work continuously. As an electronic controller unit, the static switch can be enabled immediately to replace the inverter in supplying uninterrupted power to the load. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 48: Features Of The Ups

    2.3. Features of the UPS Eaton UPS has a variety of features to ensure cost effectiveness, and consistent and reliable power supply protection. This section will provide a brief summary about the standard features of the UPS. 2.3.1. Advanced Battery Management(ABM)
  • Page 49: Power Supply Management Software

    UPS power ratings. UPS cabinets can be connected in parallel to form a larger system. Parallel connection of 4 cabinets is supported. In the case of more than 4 cabinets, please contact Eaton’s solution team for a power distribution design.
  • Page 50: Chapter 3 Ups Installation Plan

    Installation Checklist). 7. Eaton customer service engineers will carry out preliminary operational inspections and startup. NOTE Commissioning must be carried out by the customer service engineers of Eaton, otherwise, the warranty Chapter 9 provisions in will become invalid. Provision of this service is part of the sales contract on the UPS.
  • Page 51: Site Preparations

    • The UPS shall normally operate at an altitude lower than 1,000m (3,300ft.). If it is to be used at an altitude over 2,000m (6,600ft.), please call at Eaton’s hotline for more information. • The warranty shall be invalid for failure to follow this guideline.
  • Page 52: Table 3-1: Dimensions And Weights

    When ignored, either one of these aspects can create an undesirable microclimate at the UPS location. If the environment created by this microclimate exceeds the Eaton UPS operating specification, the UPS reliability, over time, will be reduced. These same environmental extremes will also create reliability concerns for any servers that are exposed to them.
  • Page 53: Figure 3-1: Clearance For The Ups Cabinet

    * Wiring might need larger space. The picture takes a 60kW cabinet as an example Figure 3-1: Clearance for the UPS cabinet. • If D3 clearance available is smaller than 600mm, please contact Eaton service team. • Refer to Table 3-2 Figure 3-1 for clearance details.
  • Page 54: Figure 3-2: Ups Dimensions (15-40K)

    Top View Rear View Front View Right View Bottom View Figure 3-2: UPS dimensions (15–40k) Unit: mm Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 55: Figure 3-3: Ups Dimensions (60-80K)

    Eaton 93PR 15-80 kW UPS Installation and Operation Manual Top View Rear View Right View Front View Bottom View Figure 3-3: UPS dimensions (60–80k) Unit: mm Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 56: Power Supply And Wiring Preparation Of The Ups System

    • When the N wire is disconnected, all phase lines shall be disconnected as well. The wire with appropriate size shall be used to facilitate future upgrade. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 57 1×10 1×10 1×16 1×16 1×50 1×50 size) Grounding 1.0 time Neutral wire (N) (AC/load) (nonlinear 1.7 times load) Backfeed protection Electrical clearance upon breaking of contact: ≧2.0mm device Break time: ≦15s Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 58: Table 3-4: Requirements On 15-20K Connecting Terminals And Torque

    2 (17.7) 13.3 mm²(M5) Battery (+) 2 (17.7) 13.3 mm²(M5) DC input Battery (-) 2 (17.7) 13.3 mm²(M5) Battery (N) 2 (17.7) 13.3 mm²(M5) User grounding Grounding 15 (133) 60 mm²(M8) Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 59: Table 3-5: Requirements On 30-40K Connecting Terminals And Torques

    2 (17.7) 13.3 mm²(M5) Battery (+) 15 (133) 60 mm²(M8) DC input Battery (-) 15 (133) 60 mm²(M8) Battery (N) 15 (133) 60 mm²(M8) User grounding Grounding 15 (133) 60 mm²(M8) Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 60: Table 3-6: Requirements On 60-80K Connecting Terminals And Torques

    The overcurrent protection switches for the bypass and output shall be provided by the customer. • For wiring diagram of the UPS, see Section Internal structure of UPS system. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 61: Preparation For Ups Interface Wiring

    The external alarm relay needs to connect with a switch with a rated current of 5A, a rated voltage of 30VAC (RMS)/30VDC. • The wire size of the external alarm relay shall not be smaller than 0.75 mm². Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 62: Chapter 4 Ups System Installation

    UPS and AC mains shall be provided by customers. The installation inspection and initial startup of the UPS shall be carried out by Eaton customer service engineers. Battery cabinets can be performed by qualified service personnel of the equipment manufacturer or agent.
  • Page 63 During the installation waiting period, the unpacked cabinet shall be protected against moisture, dust and other contaminants. The warranty does not cover any damages caused by failure to properly store or protect the UPS. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 64: Figure 4-1: 15-40K Unpacking Diagram

    2-3. Remove the carton, cushioning materials and damp-proof bag 5. Move the equipment onto the ground 4. Remove the screws fixing the equipment and the retaining rack at the bottom Figure 4-1: 15–40k unpacking diagram Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 65: Figure 4-2: 60-80K Unpacking Diagram

    At last, at the bottom slowly slide the equipment onto the ground along the slope board Figure 4-2: 60–80k unpacking diagram Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 66: System Installation

    Installation of external battery cabinet. WARNING Remember to lay the wires on both sides of the cabinet to prevent it from blocking the hot air venting area in the rear part. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 67: Figure 4-3: Gland Plate And Connector Locations

    Battery - Grounding screw Grounding terminal Output Bypass Battery + Input Battery N Battery - Details of the terminal block of 30–40K Figure 4-3: Gland Plate and Connector Locations Grounding terminal Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 68: Figure 4-4: Locations Of Cover Plate And Connecting Terminals (60-80K)

    (try to adjust it downward as much as possible) Strapping hole Battery - Output Battery N Battery + Grounding terminal Grounding terminal Input Bypass Figure 4-4: Locations of cover plate and connecting terminals (60–80k) Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 69: Installation Of External Battery Cabinet

    5. Please see the instructions of the manufacturer regarding the battery cabinet. WARNING Ensure correct connection of the positive and negative poles of the battery! Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 70: Supported Battery Configurations

    4.5. Wiring of the UPS Parallel System The rated power of each UPS must be identical, and the rated power of each equipment’s static bypass shall also be identical. If exceeding the specified quantity, please contact Eaton’s solution team for a power distribution design.
  • Page 71 The rectifier input and bypass input are separate power supplies. The power supply must use a common N wire. Battery connection In the case of parallel use of Eaton 93PR UPS 15–80k, both common battery and separate battery configu- rations are supported among the cabinets. Please see Section 4.2.1 for information about supporting com- mon battery configuration.
  • Page 72: Control Signal Overview

    Each UPS bears 3 sets of signal inputs which can configure the functions. These functions may affect the UPS in every system. Wiring of the parallel EPO switch It’s recommended that each parallel unit uses a separate EPO circuit. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 73: Installation Of The Parallel Control Wiring

    Figure 4-6 represents the parallel wiring diagram and not the physical layout plan. UPS can be arranged in any physical order. • The connection cables used among parallel UPS units shall be of shielded twisted-pair cables. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 74: Chapter 5 Communication Interfaces

    ④ : CN12 - This standard function can be used to connect the external alarm signal to the corresponding termi- nals of the UPS, e.g., smoke alarm or overheat alarm signal. Please use twisted-pair wires to connect the alarm device and the corresponding UPS terminals. For external alarm signal configuration, please consult Eaton’s ser- vice personnel.
  • Page 75 ⑧ : 1. Upon a slight touch of the button, the auxiliary battery power supply will be activated. 2. If the output of the UPS is hot(online mode/ESS mode), press the button for 10s, the UPS will transfer to bypass. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 76: Mini-Slots

    2 additional digital inputs. Warning limits for temperature and humidity can be configured in the network card and monitored in a real-time manner with Eaton’s IPM and IPP software. Temperature compensation for lead-acid battery can be achieved as well.
  • Page 77: Figure 5-4: Industrial Gateway Card

    • Industrial Gateway Card Eaton Industrial Gateway Card is integrated with many functions of SNMP card, for example, the functions of SNMP agent, HTTP/Web server, and Modbus card. Combined with Building Management System (BMS), it can provide continuous, reliable and accurate remote monitoring service to the UPS system. The user can define remote power-off, uninstallation and other tasks, and receive the system alerts from the UPS in real-time and remotely.
  • Page 78: Intelligent Power Manager (Ipm) Software

    IPM can perform remote monitoring and manage the UPS. IPM allows the user to check the power equipment within an international enterprise through a PC. The software supports monitoring of single and multiple (if web-based) Eaton UPS systems or other brands, intelligent power distribution units (ePDUs), other power and environment devices, and supports virtual environments.
  • Page 79: Chapter 6 Ups Operating Instructions

    Before UPS startup, please make sure that all installation work has been completed, and that the initial startup has been performed by Eaton’s customer service engineers. Before the initial startup, check all electrical connections to ensure successful installation and normal operation of the system.
  • Page 80: Figure 6-1: Ups Controls And Indicators

    The picture takes a 80kW cabinet as an example UPS status indicator lamp Control panel Figure 6-1: UPS Controls and Indicators Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 81: Use Of Lcd Control Panel

    System status indicator lamps: The status indicator lamps on the UPS control panel inform the operator of the current status of the UPS in the form of lights, similar to the event buzzer Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 82: Use Of Touch Screen

    Those areas will be discussed in the following sections. Figure 6-2: Components of the touch screen (Home interface) A. In the UPS status area, the model of the Eaton equipment, current date, time, and active log information are displayed.
  • Page 83: Meters

    (per phase), input power (per phase), and total frequency as well as total kVA, total kW, and power factor measurements of the bypass. The “Battery” screen displays the battery voltage, cell voltage, battery current, and Battery more. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 84: Figure 6-4: Input Interface

    Figure 6-4: Input interface Figure 6-5: Output interface Figure 6-6: Bypass interface Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 85: System Control Instructions

    UPS status and battery status. On “UPM” screen, you can view UPM status, UPS status, and battery status; or shut down the UPM. Figure 6-8: Password verification interface Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 86: Figure 6-9: System Interface

    Click “OK” button to switch to the bypass mode, as shown in Figure 6-10 . It is the same for other button functions. Figure 6-9: System interface Figure 6-10: Switch to bypass interface Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 87: Figure 6-11: Confirmation Interface

    Figure 6-14 . When the button is gray, it indicates that this button is currently null. The UPM will be shut down upon a click of the “Shutdown” button on the interface. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 88: Use Of Log Menu

    On the “History Log” screen, you can view all active logs, 1,024 items on 205 pages History Log at most. On the “Clear Log” screen, you can clear all the alert information on the “Active Log” Clear Log interface. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 89: Figure 6-15: Active Log Interface

    Figure 6-15: Active Log interface Figure 6-16: History Log interface Click “Clear All Active Logs” button on the interface, then all active logs will be removed. Figure 6-17: Clear Log interface Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 90: Use Of Info. Menu

    “Next” to enter the Setting interface. On the Setting interface, you can not only set the language, time, brightness, output voltage and frequency, but also modify the password: Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 91: Figure 6-20: Password Verification Setting Interface

    The initial password is “1111”, which can be used to enter the control interface. Setting password The initial password is “0101”, which can be used to enter the Setting interface. Figure 6-20: Password verification setting interface Figure 6-21: Setting interface Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 92: Figure 6-22: Setting - General Interface

    Save button. Click the Cancel button to return to the “General” interface. The method can be used to set other parameters. Figure 6-23: Setting - General - Time interface Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 93: Figure 6-24: Setting - Output Interface

    Eaton 93PR 15-80 kW UPS Installation and Operation Manual Figure 6-24: Setting - Output interface Figure 6-25: Setting - Meters interface Figure 6-26: Setting - Password interface Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 94: Figure 6-27: Control Password Modification Interface

    “Wrong password” will be prompted on the interface, which means that you need to re-enter a password, as shown in Figure 6-30 Figure 6-27: Control password modification interface Figure 6-28: Control password modification interface Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 95: Figure 6-29: Control Password Modification Interface

    “OK” button on the keyboard. If the password is verified, “New password has been saved” will be prompted on the interface; if the entered password is wrong, “Wrong password” will be prompted on the interface, which indicate you must re-enter a password. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 96: Use Of Service Reminder Function

    If all the four service reminders have expired, click “Remind me in 6 months” or “Remind me in 1 month”, and then the four service reminders will be enabled again on the set date and time. Click the “Learn more” button to see the detail tips. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 97: Figure 6-33: Service Maintenance Reminder Setting Interface

    Installation and Operation Manual Figure 6-33: Service maintenance reminder setting interface The service reminder can be set on the submenu under General, as shown in Figure 6-21 Figure 6-34: Location of service reminder function Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 98: Figure 6-35: Service Reminder Settings Page

    The operation method is the same for the other three service reminder pages. Figure 6-36: Fan replacement reminder settings Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 99: System Operation

    When the UPS is in “Bypass” mode, the critical load is not protected if any bypass interruption or exception occurs. 1. Check and ensure that the rectifier input switch, the output switch and the bypass switch are Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 100: Switch From "Online" Mode To "Bypass" Mode

    Otherwise, the UPS system will switch to online mode. 3. At this point, the UPS works in online mode and the online status indicator lamp is lit, and the system status displayed is “Online Mode”. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 101: Switch From "Online" Mode To "Ess" Mode

    UPS (including bypass) is at the shutdown status until it is restarted. Steps of performing “LOAD OFF”: 1. Select “Control” on the menu, and enter the password to access the control interface; Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 102: Single-Ups Operation

    (if the UPS is equipped with such a switch), then close the front door; 2. Turn on the external input distribution switch; Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 103: Ups Shutdown

    1. Click the “Control” button on the main page to switch to the “System Control” page; 2. Press the “UPS Control” button on the “System Control” page; 3. Press “Charger On” or “Charger Off” on the “UPS Control” page. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 104: Use Of Remote Emergency Power Off (Repo) Switch

    UPS output. NOTE Below are the instructions about Eaton REPO switch. In the case of REPO switch provided by the customer, the activation method might be different. Please see the operation instructions delivered together with the switch.
  • Page 105: Transfer The Ups From Double Conversion Mode To Maintenance Bypass Mode

    Maintenance bypass switch (MBS) Output switch Maintenance bypass input Figure 6-38: Switch status in maintenance bypass mode Static bypass input Maintenance bypass switch (MBS) Output Maintenance bypass input Copyright © 2022 Eaton Corporation plc. All rights reserved. Static bypass input...
  • Page 106: Switch From "Maintenance Bypass" Mode To "Online" Mode

    Rectifier input UPS operation in “Online Mode” Output switch Maintenance bypass switch (MBS) Maintenance bypass input Static bypass input Output Rectifier input Output switch Figure 6-40: Switch status in online mode Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 107: Chapter 7 Ups Maintenance

    UPS module. WARNING • The maintenance shall be performed by Eaton customer service engineers. • The voltage is lethal. Stop using the UPS when the cabinet door is opened or the protective plate is removed.
  • Page 108: Carry Out Preventive Maintenance

    Remove the filter screen from the front panel and clean it, or replace it with a new one. d. Install front plate and lock screws. 3. Log the results of the check and any corrections. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 109: Figure 7-1: Location Of 15-40K Air Filter Screen

    Eaton 93PR 15-80 kW UPS Installation and Operation Manual Air filter screen Figure 7-1: Location of 15–40k air filter screen Air filter screen Figure 7-2: Location of 60–80k air filter screen Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 110: Regular Maintenance

    Pay special attention to the wire crimping terminals, and fasten them during maintenance. 7.2.4. Annual maintenance The annual preventive maintenance shall only be performed by Eaton customer service engineers who are familiar with UPS system maintenance. For more information about maintenance items, please contact your customer service representative. 7.2.5.
  • Page 111: Maintenance Training

    7.4. Maintenance Training Eaton provides basic training courses to help users grasp UPS operation knowledge and the method for preliminary corrective maintenance. Please contact the customer service representative for detailed information of training and other services.
  • Page 112: Chapter 8 Technical Indicators Of Product

    IEC 61000-4-8 (Power frequency magnetic field) IEC 61000-4-11(Voltage dips and Voltage interruptions) Performance & Tests IEC 62040-3 2011 Environmental IEC 62430 RoHS 2002/95/EC WEEE 2002/96/EC ECO Design Directive 2009/125/EC Batteries 2006/66/EC Packing: 94/62/EC Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 113: Ups Input

    126–150% load 1min; >151% load 150ms. Output current See Table 3-3 : Rated current at rated power and voltage Rated load power factor Load power factor (allowed) Lag 0.7 to lead 0.7 Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 114: Battery Specifications

    The storage area must be protected from rain, water, chemicals and the ambient gases provided in Table 8-1 , and meet the requirements (see Table 8-2 ) on the transportation and storage environment for 1 year. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 115: Table 8-2: Requirements On The Environment For Transportation And Storage Within 1 Year

    Stored with initial packaging Others If the actual storage conditions of the machine do not meet the above storage environment, re- evaluate the storage time according to the actual storage environment. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 116: Chapter 9 Warranty

    WARRANTY Commitment of Eaton: Eaton provides 24 months of warranty starting from the date of startup of the equipment (which shall be performed by Eaton or the engineer authorized by Eaton within 3 months after delivery), or subject to the agreement.
  • Page 117: Chapter 10 Installation Checklist

    The air-conditioning device has been installed and its operation is normal.  The surrounding area of the UPS’ installation site shall be clean and free of dust. (Eaton recommends that the UPS is  installed on a level floor suitable for computer or electronic equipment).
  • Page 118  There is adequate workspace around the UPS and other cabinets.  The startup and operational inspection of the parallel system or accessory case shall be performed by Eaton customer  service engineers. The positive, negative and neutral wires of the battery shall be installed correctly and properly.
  • Page 119: Table 10-1: User Settings

    1 disabled NTP clock setting. Screen saver interval 10min, non-configurable. HMI backlight Adjust the backlight brightness. Configuration of “setting password” The default password is 0101. Configuration of “control password” The default password is 1111. Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 120 . . Copyright © 2022 Eaton Corporation plc. All rights reserved.
  • Page 122 614-40185-00...