Figure 3-1: Ups Cabinet Clearances. See Table; Table 3-2: Ups Cabinet Minimum Clearances - Eaton 93PR Installation And Operation Manual

Table of Contents

Advertisement

The UPS cabinets use forced air cooling to regulate internal component temperature. You must
allow clearance in front of and behind each cabinet for proper air circulation.
The clearances required around the UPS cabinet in both of these situations are shown in
Table 3-2

Table 3-2: UPS Cabinet Minimum Clearances

From Top of Cabinet
From Front of Cabinet
From Back of Cabinet
* Cabling may require more space.
** Service space (when the two sides are not against other cabinets, the 300kW top air configuration UPS can be
installed against the wall).
D1
Copyright © 2021 Eaton Corporation plc. All rights reserved.
.
Rear Exhaust Clearance
300 mm
D1
1000 mm
D2
800 mm*
D3
D3
D2
Figure 3-1: UPS Cabinet Clearances. See
Eaton 93PR 60-1200 kW UPS
Installation and Operation Manual
Top Exhaust Clearance
800 mm
1000 mm
600 mm**
The picture takes a 600kW cabinet as an example
D1
D3
D2
Table 3-2
.
27