The basic environmental requirements for operation of the UPS system are:
Ambient Temperature Range: from +0°C to +30°C, To ensure that your UPS functions well,
please operate it in an environment with an ambient temperature ranging between 0 - 30°C.
If the ambient temperature exceeds 30°C, the UPS should be de-rated by 12% for every
increase of 5°C in the temperature; the maximum ambient temperature should not exceed
50°C as UPS operating with loads in high-temperature environments for a long time will result
in the reduction of the battery life. For example, if the UPS working environment temperature
is 35°C, the load must be less than 88%. If it exceeds 90%, the UPM will shut down.
Recommended Operating Range: from +20°C to +25°C
Maximum Relative Humidity: 95%, non condensing
The room where the UPS is placed must meet the following air circulation requirements:
For 300KWUPS, air flow need be not lower than 3400M
For 600KWUPS, air flow need be not lower than 6800M
For 1200KWUPS, air flow need be not lower than 13600M
The UPS ventilation requirements are shown in the following table:

Table 3-3: Air conditioning or Ventilation Requirements During Full Load Operation

Rating
300 kW
600 kW
1200 kW
28
Heat Rejection (Kcal/hour)
10748
21496
42993
3
/h;
3
/h;
3
/h;
Heat Rejection (BTU/h x 1000)
42.67
85.3
170.65