Page 4
The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts) without the written approval of Eaton Corporation. Every care has been taken to ensure the accuracy of the information contained in this manual, but no liability can be accepted for any errors or omission. The right to make design...
SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference. The UPS operates with mains, battery or bypass power. It contains components that carry high currents and voltages.
• LV Directive (Safety) 2006/95/EC • EMC Directive 2004/108/EC Declaration of conformity with UPS harmonised standards and directives EN 62040-1 (Safety) and EN 62040-2 (EMC) are available at http://powerquality.eaton.com or by contacting your nearest Eaton office or authorized partner. 25-75 kW User's and Installation Guide...
User Precautions The only user operations permitted are: • Start up and shut down of the UPS, excluding the commissioning start up. • Add or replace the hot-swappable UPM(s). • Use of the LCD control panel and Maintenance Bypass Switch (MBS). • Use of optional connectivity modules and their software. The user must follow the precautions and only perform the described operations. Any deviation from the instructions could be dangerous to the user or cause accidental load loss. WARNING The user is not permitted to open any screws excluding connectivity plates and the MBS locking plate. Failure to recognise the electrical hazards could prove fatal.
Symbols on the UPS and Accessories The following are examples of symbols used on the UPS or accessories to alert you to important information: RISk OF ElECTRIC SHOCk - Indicates that a risk of electric shock is present and the associated warning should be observed.
For More Information Address any inquiries about the UPS and battery cabinet to the local office or agent authorized by the manufacturer. Please quote the type code and the serial number of the equipment. Call your local service representative if help is needed with any of the following: •...
AC power to critical load and protects it from power failures. Eaton 93PR has flexible power scalability from 25 kW to 300 kW, hot swappable modular and standard design, high flexibility and applicability, market leading efficiency, availability and performance, very suitable to applications of micro data center (MDC), small-middle-large data center, automation, medical etc.
Figure 2-1: Eaton 93PR UPS looking Inside the UPS System The system level static bypass in the Eaton 93PR UPS cabinet determines the attainable output power of the UPS. The static bypass line consists of static switch and a backfeed protection isolation device connected in series.
The UPS is including rectifier input switch, output switch, bypass switch and MBS switch, N as default. And for internal battery version, battery breaker will be as standard units. If utility power is interrupted or falls outside the parameters specified in Chapter 8 Technical data, the UPS uses a backup battery supply to maintain power to the critical load for a specified period of time or until the utility power returns.
Internal relay contacts Figure 2-4: Path of current through the UPS in double Conversion Mode Three-phase AC input power is converted to DC using a multilevel converter with IGBT devices to produce a regulated DC voltage to the inverter. The UPS status indicated on the display is “Unit Online” and the UPM status is “Active”...
2.2.1.2 Energy Saver System Mode In ESS mode the UPS safely provides mains current directly to the load when the input is within the acceptable limits by its voltage and frequency. The UPS status indicated on the display is “Unit Online ESS” , and the UPM status is “Active”...
2.2.2 Stored Energy and Battery Mode When running normally in double conversion or ESS mode, the UPS automatically transfers to supply the load from batteries or other stored energy source if a utility power outage occurs, or if the utility power does not conform to specified parameters.
2.3 UPS features 25-75 kW The Eaton UPS has many features that provide cost-effective and consistently reliable power User's and Installation Guide protection. The feature descriptions provide a brief overview of the UPS standard features.
2.3.2 Eaton Hot Sync Eaton Hot Sync technology is an algorithm that eliminates the single point of failure in a parallel system and therefore enhances the system reliability. The Hot Sync technology is incorporated in all Eaton 93PR UPSs, and it is utilised in both multi-module internal parallel and external parallel systems.
2..3.4 Variable Module Management System (VMMS) Eaton Variable Management Module System (VMMS) is a key component of Eaton EAA. Eaton VMMS technology maximizes UPS efficiencies at low load levels while supporting the load with continuous double- conversion power but increase the system efficiency by dynamic adjusting the UPM active and idle.
Load Sync Enable pushbutton on the front of the panel. When enabled, the Load Sync Enable pushbutton illuminates. The Eaton Sync Control panel provides a three phase synchronization reference to each system. Each system uses this reference to regulate the inverter phase relationship so that the two system outputs can maintain synchronization with each other.
93PR 25-75 kW units The Eaton 93PR25-75kW UPS is including internal battery version and external battery version. The external battery version UPS supports external batteries. For detailed battery specifications, see Chapter 8 Technical data.
UPS Internal Options The following table shows different standard and optional UPS options and the models where they apply. Table 2-2: Standard and Optional UPS Options 25-75 kW 25-75 kW Without Internal Battery With Internal Battery Version Version Smart touch screen display for system Standard Standard control and monitoring...
4. Unload and install the UPS cabinet, and wire the system 5. Complete the installation checklist (Chapter 10 Installation checklist) 6. Have authorized service personnel perform preliminary operational checks and startup. NOTE Startup and operational checks must be performed by an authorized Eaton Customer Service Engineer, or the warranty terms specified in Warranty become void. This service is offered as part of the sales contract for the UPS. Contact service in advance (usually a two-week notice is required) to reserve a preferred startup date. Creating an Installation Plan Before installing the UPS system, read and understand how these instructions apply to the system being installed.
The UPS cabinets use forced air cooling to regulate internal component temperature. By standard, air inlets are in the front of the cabinet and outlets are in the back. You must allow clearance in front of and behind each cabinet for proper air circulation. The clearances required around the UPS cabinet in both of these situations are shown in Table 3-3: UPS cabinet minimum clearances.
The basic environmental requirements for operation of the UPS system are: • Ambient Temperature Range: from +5 to +40 °C • Recommended Operating Range: from +20 to +25 °C • Maximum Relative Humidity: 95 %, noncondensing It is required to arrange ventilation of the UPS room. Sufficient amount of air cooling is needed to keep the maximum room temperature rise at desired level: • Temperature rise of max. +5 °C requires the airflow of 600 m³ per 1 kW of losses • Temperature rise of max. +10 °C requires the airflow of 300 m³ per 1 kW of losses An ambient temperature from +20 to +25 °C is recommended to achieve a long life of the UPS and batteries.
Left View Front View Right View Right view Front view Left view Top View Top view Figure 3-3: UPM dimensions 3.2.2 UPS System Power Wiring Preparation NOTE If installing a maintenance bypass, a minimum of two separate feeds with upstream feeder breakers, or a single feed with two upstream feeder breakers, must be provided: one for the UPS or rectifier input breaker (if installed) and one for the maintenance bypass input. DO NOT use a single feed or a single feeder breaker to supply both the UPS or rectifier input breaker and the maintenance bypass. If a bypass input breaker is installed in the maintenance bypass and a single-feed UPS is being installed, a single feed to the maintenance bypass is acceptable for supplying both the UPS and the bypass.
• Specification is for copper wire with a 90 °C rating. • The bypass feed into this equipment uses four wires. The rectifier feed into this equipment uses three or four wires. The phases must be symmetrical about ground (from a Wye source) for proper equipment operation. • If the load requires a neutral, a bypass source neutral must be provided. If the load does not require a neutral and there is no neutral conductor connected at the bypass input, a neutral must be installed to source star point. • A readily accessible disconnect device must be incorporated in all fixed input wiring.
See the following table for power cable terminations. Table 3-8: UPS Power Cable Terminations Terminalfunction Terminal Function TighteningtorqueNm Check the tightening torque AC input to UPS rectifier MAINS INPUT L1,L2,L3,N from the connector label. BYPASS Check the tightening torque AC input to bypass L1,L2,L3,N from the connector label. INPUT Check the tightening torque UPS output...
3.2.3 UPS System Interface Wiring Preparation Control wiring for features and options should be connected at the customer interface terminal blocks located on top front of the UPS, behind the door. dANGER Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is required. Read and understand the following notes while planning and performing the installation: •...
Unpacking and Unloading the UPS If the equipment has been transported in the upright position the outside ’Tip&Tell’ indicator on the package surface should be intact. If the arrow has turned all blue, contact the appropriate parties for reporting inappropriate transportation. NOTE •...
Page 41
8. Secure the UPS cabinet in position by lowering the leveling feet until the cabinet is not resting on the casters and the cabinet is level. 9. If permanently mounting the system, proceed to Step 11; 10. Using the retained hardware, reinstall the shipping brackets removed in Step 2 and Step 5 to the front and rear of the UPS cabinet with the angle facing outward (see Figure 3-4 and Figure3-5).
Front Door Leveling Feet Leveling Feet Rear Shipping Front Shipping Bracket Bracket Left Shipping Bracket Leveling Feet Right Shipping Bracket Leveling Feet Figure 3-4: Remove all Fixed Shipping Brackets and Screw Fixed on the Pallet UPS Cabinet Pallet Ramp (side panel from wood container) Figure 3-5: Attaching the Ramp to the Pallet Figure 3-6: Rolling the Cabinet Down the Ramp 25-75 kW User's and Installation Guide...
Instruction for Femoving the UPM Module Packaging 1. Cut off the packing strap and open the carton (see Figure 3-7); 2. Lift the foam on the UPM module upward to remove them (see Figure 3-7); 3. Take out the UPM module (see Figure 3-7). NOTE The UPS is heavy. It requires two people for transportation due to its weight.
Instruction for Removing the Battery Module Packaging 1. Cut off the packing strap and open the carton (see Figure 3-8); 2. Lift the foam on the Battery module upward to remove them (see Figure 3-8); 3. Take out the Battery module (see Figure 3-8). NOTE Heavy unit. It must be carried by two people at the same time to avoid injury.
UPS SYSTEM INSTAllATION The customer has to supply the wiring to connect the UPS to the local power source. The electrical installation procedure is described in the following section. The installation inspection and the initial start-up of the UPS and installing an extra battery cabinet must be carried out by qualified service personnel such as a licensed service engineer from the manufacturer or from an agent authorized by the manufacturer.
BAT + DC input BAT – UPS output Mains input to Rectifier Mains input to Bypass Top view Control signal line entrance Control signal junction Power line entrance Power terminal block Front view Back view Figure 4-1: 93PR 25-75 kW Gland Plate and Connector Locations (With Internal Battery Version) 25-75 kW User's and Installation Guide...
BAT + DC input BAT – UPS output Mains input to Rectifier Mains input to Bypass Top view Control signal line entrance Control signal junction Power line entrance Power terminal block Front view Back view Figure 4-2: 93PR 25-75 kW Gland Plate and Connector Locations (Without Internal Battery Version) 25-75 kW User's and Installation Guide...
Battery System Installation Internal Battery Installation Connection of these batteries is to be left to the responsibility of the commissioning personnel in order to avoid damages to the equipment or personal injuries in case of an incorrect connection. The batteries are designed to deliver a large amount of energy and an incorrect connection may lead to short circuit and cause serious injuries to the personnel or damages to the equipment.
NOTE • Lock the knob to the locked state, when the battery modules are pushed into the battery box. • Install the battery modules from the bottom to the top. Install all the battery modules Install one battery module Figure 4-5: Install the Battery Module 25-75 kW User's and Installation Guide...
Page 50
The default battery settings of the UPS are for 12 VDC VRLA batteries. If requested to use other battery types, contact your Eaton representative. For the battery specification, see Chapter 8.4 Battery specification. Connect the battery cabinet as follows: 1.
4.3 Installing a Remote EPO Switch A remote EPO switch can be used in an emergency to shut down the UPS and remove power to the critical load from a location away from where the UPS is installed. EPO is to be connected to the UPS’s top front panel, on connector EPO. Below are the NO and NC connections of the EPO switch.
External Battery Breaker Wiring Interface When using the original battery cabinet from the EATON, the battery breaker interface wiring is provided with the cabinet. Connecting it requires only routing the wires from the cabinet to the bottom section of the UPS.
Mini-slot Interface Connections For Mini-slot accessories and communication devices selection see Chapter 5 Communication interfaces. For installation and setup of a Mini-slot card, please contact your Eaton representative. To install wiring to connections: 1. If not already installed, install the LAN and telephone drops.
4.5 Wiring Parallel 93PR UPS Systems The outputs of multiple 93PR UPS systems can be connected in parallel. Up to four (4) units can be paralleled. The UPS static bypass power rating needs to be identical among all paralleled units. However, paralleled UPS cabinets can be housed with different number of UPM power modules.
MOB’s Module Output Breakers (MOBs) allow the output of the UPS to be disconnected from the other UPSs and system load for maintenance and service. Design considerations assume that each UPS has a Module Output Breaker (MOB). The breaker shall not disconnect neutral. The MOB must have a “N.C”...
4.5.2 Control Signals Overview Two controls signals (External CAN Network, Bypass Pull-Chain) are required for external paralleling. Both of these control signals are fault tolerant and alarmed when disconnected. External CAN (ECAN) ECAN provides means for communications between the UPS’s in a parallel system. The system will continue to share load and protect the load when this network fails.
Figure 4-9: Pimplified CAN and Pull-Chain Wiring for Parallel UPP System NOTE This drawing is for distributed bypass wiring purposes and is not a floor layout plan. UPPs can be placed in any physical order. NOTE External CAN connections between UPPs require shielded twisted pair wire. NOTE Use twisted pair wiring between the UPP and MOB AUX contacts. Figure 4-10: CAN and Pull-Chain Wiring for Parallel UPP With MOBs 25-75 kW User's and Installation Guide...
Figure 4-11: CAN and Pull-Chain Wiring for Parallel UPP Without MOBs NOTE NC and NO designations on MOB AUX contacts are defined with breaker in OFF (open) position. If MOB contacts have pigtail leads, use the same wire gauge to connect to the UPP and use the correct crimp connections for the wire gauge. External CAN connections between UPP cabinets require shielded twisted pair wire. Use twisted pair wiring between the UPP and MOB AUX contacts. Always confirm contact operation prior to wiring. 25-75 kW User's and Installation Guide...
4.5.4 Installing Eaton Sync Control Eaton Refer to the operating instructions provided with the Sync Control. On Bypass Common UPS System−A – On Bypass NO UPS System−B – On Bypass NO UPS System−A – Bypass Voltage Phase A UPS System−A – Bypass Voltage Phase B UPS System−A –...
COMMUNICATION INTERFACES This section describes the communication features of the Eaton 93PR UPS. The UPS has the following communication interfaces: Mini-slot 1 Mini-slot 2 Mini-slot 3 USB device (connection to computer) Emergency Power Off (EPO) Relay output USB host (connection to accessories)
Mini-slots The Eaton 93PR UPS has three Mini-slot communication bays. The UPS is compatible with the following Mini-slot cards: • Network Card-MS Provides remote monitoring through a Web browser interface, e-mail, and a network management system (NMS) using SNMP and connects to a twisted-pair Ethernet (10/100BaseT) network.
• Relay Card-MS Two types of interfaces via a DB9 connector are available with this card. Dry contact mode provides a simple way to transmit UPS information to an alarm system, PLC, or computer system via dry relay contacts. By default the transmitted information is load powered, load on bypass, load on battery, load on utility, battery fault, and low battery.
(IPP) application provides automatic, graceful shutdown of computers and virtual machines or servers powered by an Eaton UPS during a power outage that lasts longer than your available battery runtime. Intelligent Power Protector can be remotely supervised and managed by the Intelligent Power Manager (IPM) application.
Read these instructions and have a thorough understanding of UPS operation before attempting to operate any of the controls. • The UPS is configured to operate with one of following nominal voltages: 380, 400, or 415 VAC. • Before operating the UPS, confirm the UPS nominal voltage and frequency from display by selecting Settings -> Info. • If the UPS need to be operated with another voltage or frequency, contact your closest Eaton office or Eaton authorized partner. NOTE The UPS in not a measuring device. All displayed measurements are only approximate values. 25-75 kW User's and Installation Guide...
UPS Controls and Indicators 6.1.1 Control Panel The control panel, located on the UPS front door, contains a color touch screen display. It is used to display the status of the UPS system and control the operation of the UPS. Figure 6-2: Parts of the display The display consists of the following parts: • A: Status bar...
6.1.2 Status Indicators The four symbols below the display are status indicators. They are colored light emitting diode (LED) lamps, and they work in conjunction with the alarm horn to let you know the operating status of the UPS. Indicator Status description The UPS is operating normally and...
Normal indicator also remains illuminated. Figure 6-3: Yellow symbol — battery mode 6.1.3 UPS Status Lights The LED Power Show (LPS) consists of two rows of LEDs located on the left and right sides of the UPS cab- 6.1.2 Status indicators net door.
Steps to Operate the UPS Table 6-1: UPS Menu Structure Main menu Submenu Functions An overview of UPS operation, including information on load, Home efficiency and consumption. Meters summary A summary of the UPS or sys-tem meters. Input meters Detailed information on UPS or system input meters. Meters Bypass meters Detailed information on UPS or system bypass meters.
Signing In If the level 1 password is enabled, you need to sign in. 1. Press the lock button in the upper right corner of the screen. 2. Type your passcode and press Ok. 3. You are signed in. Press Continue to return to the previous screen. There are three attempts to input the password.
System Control Instructions 6.4.1 Starting the UPS System in Double Conversion Mode The UPS system can consist of a single UPS or several parallel UPSs. UPSs with their MOB open are not considered as part of the system. To start the UPS system: 1.
6.4.2 Starting the UPS System in Bypass Mode If the inverter output of the UPS is not available and the critical load needs to be energized, peform the following procedure: CAUTION In Bypass Mode, the critical load is not protected from commercial power interruptions and abnormalities. 1. Unfasten the front door latch and swing the door open. 2.
6.4.5 Transfer from Double Conversion Mode to Energy Saver System Mode Note that the Energy Saver System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. To transfer the critical load to Energy Saver System mode: 1.
2. Perform the LOAD OFF procedure (see Chapter 6.4.8 De-energizing the Critical Load. The input, output, and bypass backfeed contactors open, the battery breaker or disconnect is tripped, and the power module is turned off. dANGER Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened. 3. Unfasten the front door latch and swing the door open. 4.
UPS Control Instructions 6.5.1 Starting a Single UPS Ensure that load level does not exceed single UPS capacity. To start the UPS 1. Unfasten the front door latch and swing the door open. 2. Verify that rectifier input switches, bypass input switch, neutral switch are closed if included inside the UPS system, and verify that battery breaker is closed.
6.5.2 UPS Shutdown A single UPS in the system can be shut down only if it is redundant. In practice that means a UPS is not allowed to be shut down if doing so would lead to an overload condition in the remaining UPSs in the system. To shut down a single UPS: 1.
Page 77
Note: • The “Permitted Maximum Power” does not mean that the UPS will be overloaded if this power value is exceeded. For example, when selecting the 2+2 configuration, the rated UPS apparent power is 100kVA and active power is 100kW, therefore, if load exceeds the permitted maximum power 50kW (permitted maximum power), the UPS will not be overloaded and only the N+X (X=2) structure will be changed.
6.6.2 Starting the UPMs Make sure that load level does not exceed single UPM capacity. To start an individual power module in Double Conversion Mode: 1. Unfasten the front door latch and swing the door open. 2. Verify that rectifier input switches and bypass input switch are closed if included inside the UPS system, and verify that battery breaker is closed, and close the front door.
UPS output. The EPO switch de-energizes the critical load and powers down the UPS immediately, without asking for verification. The UPS, including Bypass, remains off until restarted. CAUTION All power to the critical load is lost when the EPO switch is activated in the following step. You should use this feature only when you want to de-energize the critical load. NOTE The following instructions are for the Eaton Corporation-supplied EPO switch. If a customersupplied EPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch. dANGER Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and cleared.
Transfer the UPS to Maintenance Bypass Mode: 1. The normal start position should be following: Maintenance bypass switch (MBS) Maintenance bypass input Static bypass input Bypass switch Rectifier input Input switch Output switch Figure 6-9: The Normal Positions of the MBS Switches and Rectifier Disconnect Switch (Must be Located in the Site Wiring) 2. Refer the chapter 6.4.3, and transfer Normal Mode to Bypass Mode. 3.
6.9 Transfer UPS from Maintenance Bypass to double Conversion Mode To transfer the UPS back to double Conversion Mode: 1.The normal start position should be the following: Maintenance bypass switch (MBS) Maintenance bypass input Static bypass input Bypass switch Rectifier input Input switch Output switch Figure 6-11: Maintenance Bypass Mode...
6.10 STS Module The STS module mainly supports the static bypass function, which includes SCR and SCR input contactors, and cooling fan. Support hot swap. NOTE Cannot disconnect and remove the STS module while the UPS is in Bypass Mode. NOTE STS module all repairs and service should be performed by AUTHORISEd SERVICE PERSONNEl ONlY. Figure 6-13: STS Module 25-75 kW User's and Installation Guide...
UPS MAINTENANCE The components inside the UPS cabinet are secured to a sturdy metal frame. All repairable parts and assemblies are located for easy removal, with very little disassembly. This design allows authorized service personnel to perform routine maintenance and servicing quickly. You must schedule periodic performance checks of your UPS system to keep it running properly.
Majority of the work must be performed by Eaton authorized service personnel. Only the actions described in Chapter 7 .2.1 DAILY maintenance and Chapter 7 .2.2 MONTHLY maintenance are allowed for the user.
7 .2.4 ANNUAL M aintenance Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact your service representative for more information about service offerings. 7 .2.5 BATTERY Maintenance Contact your service representative for battery maintenance. Battery replacement and maintenance should be performed only by authorized service personnel.
HAZARDOUS MATERIALS. Batteries may contain HIGH VOLTAGES, and CAUSTIC, TOXIC and FLAMMABLE substances. Batteries can injure or kill people and damage equipment if used improperly. DO NOT DISCARD unwanted batteries or battery material in the public waste disposal system. Follow ALL applicable, local regultions for storage, handling and disposal of batteries and battery materials. Figure 7-2: Recycling Batteries Symbol Maintenance Training For more information about training and other services, contact your Eaton representative. 25-75 kW User's and Installation Guide...
UPS System Input Table 8-2: UPS System Input Rated Input Voltage 220/380 V; 230/400 V; 240/415 V Rated input voltage -15 % / +20 % Voltage Tolerance, (Rectifier Input) Voltage Tolerance, (Bypass Input) Rated input voltage -10 % / +10 % Rated Input Frequency 50 or 60 Hz, user configurable Frequency Tolerance 40 to 72 Hz Number of Input Phases, (Rectifier Input)
UPS System Output Table 8-3: UPS System Output Number of Output Phases 3 phases + N Rated Output Voltage 220/380 V; 230/400 V; 240/415 V, configurable Total Voltage Harmonic distortion < 1 % 100 % Linear Load < 5 % 100 % Non-Linear Load Rated Output Frequency 50 or 60 Hz, configurable ±...
Battery Specification Table 8-4: Battery Specification Battery Type VRLA, 12 Vdc 40-42 blocks, 240-252 cells per battery string, default 40 blocks per battery string. Battery Quantity Note! Battery strings with different battery quantity and voltage may not be connected in parallel! 480 V (40 blocks) to 504V (42 blocks) Battery Voltage ABM or float charge...
UPS Environmental Specifications Table 8-5: UPS environmental specifications < 65 dBA in double conversion Acoustic Noise at 1 m < 55 dBA in ESS Ambient UPS Storage Temperature Range From -25 °C to +55 °C in the protective package* From +5 °C to +40 °C*, Ambient Service Temperature Range, (UPS) No output power derating required. 5 to 95 %, no condensation allowed Relative Humidity Range 5 to 95 %, no condensation allowed Maximum Service Altitude...
The warranty is only valid if the installation inspection and initial start up of the UPS unit is carried out by a service engineer approved by Eaton. Service and maintenance of the UPS shall also be performed only by a service engineer approved by Eaton.
A remote battery disconnect control is mounted in its installed location and its wiring is terminated inside the UPS and battery cabinet. (OPTIONAL) Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (OPTIONAL) Startup and operational checks are performed by an authorized Eaton Customer Service Engineer. 25-75 kW User's and Installation Guide...
APPENdIX A: USER SETTINGS The UPS has the following settings that are user modifiable. In the Home screen, select Settings. User settings: Table 11-1: User Settings To modify the Config settings, you need to sign in. Setting description Information on the UPS model, including part number Info and serial number.
Need help?
Do you have a question about the 93PR Series and is the answer not in the manual?
Questions and answers