2.1. Looking Inside the UPS System

The system level static bypass in the 93PR series UPS determines the attainable output power of the
UPS. The static bypass line consists of static switch and a backfeed protection isolation device connected
in series. In addition, there is a system level control unit that constantly monitors the power delivered
through the bypass line or to the input of the UPS. Transfers to static bypass are seamless and performed
automatically by the system as needed, for example, in case of an extended system overload.
Each UPM power module includes a rectifier, battery converter, inverter and independent controls. The
UPM is hot swappable (Hot Swap), Each UPM is able to operate and share the load independently,
despite the status of the other UPMs.
93PR 300 kW UPS includes a 300 kW rated static bypass module, maximum five n internal paralleled
UPM modules; Configurable rectifier input switch, output switch, internal maintenance bypass switch and
bypass switch, These units do not include internal batteries.
For the structure diagram of the 300kW UPS cabinet, please refer to
93PR 600 kW UPS includes a 600 kW rated static bypass module, maximum ten internal paralleled
UPM modules; Configurable rectifier input switch, output switch, internal maintenance bypass switch and
bypass switch,These units do not include internal batteries.
For the structure diagram of the 600kW UPS cabinet, please refer to
93PR 1200 kW UPS includes a 1200 kW rated static bypass module, maximum twenty internal paralleled
UPM modules. These units do not include internal batteries.
For the structure diagram of the 1200kW UPS cabinet, please refer to
For optional configuration, see section