8.2. UPS System Input

Table 8-2: UPS System Input

Rated Input Voltage
Voltage Tolerance, (Rectifier Input)
Voltage Tolerance, (Bypass Input)
Rated Input Frequency
Frequency Tolerance
Number of Input Phases, (Rectifier Input)
Number of Input Phases, (Bypass Input)
Input Power Factor
Rated Mains Input Current
Maximum Mains Input Current
Input Current Distortion at Rated Input Current, iTHD
Rectifier Ramp-up, Rectifier Start and Load Step
Backfeed Protection
122
220/380 V; 230/400 V; 240/415 V
301 ~ 478 V Line voltage
175 ~ 276 V Phase voltage
50 or 60 Hz, user configurable
40 to 72 Hz
3 phases + N (Optional)
> 0.99
See
Table 3-6
Rated and Maximum Currents for Rated
Power and Voltage (unit:A)
< 3%
5 A/s per UPM (default), configurable. Min 1A/s per
UPM
Yes, for rectifier and bypass lines