Table 3-5: Maximum Recommended Multi-Core Cable Sizes (Unit:mm 2 ) - Eaton 93PR Installation And Operation Manual

Table of Contents

Advertisement

The selection of wire diameter needs to take into account the future power upgrade of UPS.
Table 3-5: Maximum Recommended Multi-core Cable Sizes (unit:mm
Rectifier
UPM QTY
input
4*60kW
2*150
4*62.5kW
2*150
5*60kW
2*150
6*60kW
2*150
7*60kW
3*150
8*60kW
3*150
8*62.5kW
3*150
9*60kW
3*240
10*60kW
3*240
11*60kW
4*240
12*60kW
4*240
13*60kW
5*240
14*60kW
5*240
15*60kW
5*240
16*60kW
5*240
17*60kW
6*240
18*60kW
6*300
19*60kW
6*300
20*60kW
6*300
*:The UPS busbars wiring needs to be evenly divided (see
Copyright © 2021 Eaton Corporation plc. All rights reserved.
UPS
Bypass
output
input
2*150
2*150
2*150
2*150
2*150
2*150
2*150
2*150
3*150
3*150
3*150
3*150
3*150
3*150
3*240
3*240
3*240
3*240
4*240
4*240
4*240
4*240
5*240
5*240
5*240
5*240
5*240
5*240
5*240
5*240
6*240
6*240
6*300
6*300
6*300
6*300
6*300
6*300
Figure 4-9
to
Figure 4-15
for the location of the busbars).
Eaton 93PR 60-1200 kW UPS
Installation and Operation Manual
2
)
N*
Battery*
3*150
4*150
3*150
4*150
3*150
4*150
3*150
4*150
5*150
5*150
5*150
5*150
5*150
5*150
5*240
4*240
5*240
4*240
6*240
6*240
6*240
6*240
8*240
8*240
8*240
8*240
8*240
8*240
8*240
8*240
9*240
8*240
9*300
8*300
9*300
8*300
9*300
8*300
PE*
6*150
6*150
6*150
6*150
8*150
8*150
8*150
6*240
6*240
8*240
8*240
8*240
10*240
10*240
10*240
10*300
10*300
10*300
10*300
37