Enabling And Disabling The Battery Charger; Upm Control Instructions; Adding/Reducing/Replacing Modules Online - Eaton 93PR Installation And Operation Manual

Table of Contents

Advertisement

6.4.3.

Enabling and Disabling the Battery Charger

To turn the battery charger on or off, perform the following procedure:
1. Press the Controls button in the main menu. The System controls screen appears.
2. On the System controls screen, press UPS controls.
3. Press the Start charger / Stop charger button.

6.5. UPM Control Instructions

6.5.1.

Adding/Reducing/Replacing Modules Online

N+X is the most reliable power supply configuration at present. N represents the minimum
number of modules of the UPS that the total load needs; X represents the number of the
redundant modules of the UPS, i.e. the number of the fault modules that the system can handle
simultaneously. The bigger X is, the higher the system reliability is. The 93PR can be installed
up to twenty modules in its cabinet and the N+X parallel redundancy system can be configured
as 1+ 9 or 9 +1 etc multiple different modes. The UPM modules can be added, reduced and
changed online and the quantity of the N and X of the N+X parallel redundancy system can be
changed according to requirement at any time. When the modules fail, if only the quantity of the
fault modules is less than or equal to X, the fault UPM modules can be changed online without
affecting the UPS running.
Options Supplied by the N+X Parallel Redundancy System
The 93PR can be installed from 1 up to 10 UPS modules in its cabinet and the user can choose
the N+X parallel redundancy solution easily. Suppose the load is 80kVA and the optional solution
is listed in the following table:
Installed
UPM
2
2+1
2+2
2+3
2+4
2+5
2+6
2+7
10
Note:
The "Permitted Maximum Power" does not mean that the UPS will be overloaded if this power value is exceeded.
For example, when selecting the 2+2 configuration, the rated UPS apparent power is 120(100)kVA and active
Copyright © 2021 Eaton Corporation plc. All rights reserved.
Permitted Maximum Power
50kW Module
100kW
120(100)kW
120(100)kW
120(100)kW
120(100)kW
120(100)kW
120(100)kW
120(100)kW
120(100)kW
Installation and Operation Manual
60kW Module
120kW
120(100)kW
120(100)kW
120(100)kW
120(100)kW
120(100)kW
120(100)kW
120(100)kW
120(100)kW
Eaton 93PR 60-1200 kW UPS
Permitted Quantity of
the Fault UPS Modules
0
1
2
3
4
5
6
7
8
111