Nt5K83Ga E&M Tie Trunk Card - Nortel Meridian 1 Planning And Installation Manual

Table of Contents

Advertisement

Page 162 of 590
NT5K83GA E&M TIE trunk card
553-3021-209
Standard 1.00
Chapter 12 — Installing the circuit cards
LD 14 - Route Data Block
SUPN
YES, (NO)
CLS
DTN, (DIP)
Self-test
When the NT5K83FA card is installed and power is applied to it, a self-test
is performed on the card. The red LED on the card's faceplate flashes three
times, then remains continuously lit until the card is enabled in software. If
the self-test fails, the LED remains lit after the card is enabled.
The NT5K83GA card provides four trunks which can function as the
following:
4-wire E&M (Type I and II)
4-wire BPO (Type 5)
RAN
PAG
MUS
Switch settings
There are four switch settings on the E&M TIE trunk card, one for each trunk
unit.
Procedure 26
NT5K83GA E&M TIE trunk card installation
1
Set the switch settings on the card, as shown in Table 25 on
page 149.
2
Insert the card into the selected card slot and lock it in position.
3
Connect the trunk units to the cross-connect terminal by tip and
ring leads (Refer to the Tables in "Chapter 18 — Connecting the
trunks" on page 313).
4
Configure the card in software (LDs 16 and 14).
—————————— End of Procedure ——————————
July 1999
Answer and disconnect
supervision
Digitone, (Dialpulse)