Drivers, parameters, diagnostic messages and
address space
E.1

Address space for the Ex power module

E.1.1

Parameter assignment

Parameter assignment in the user program
You can re-configure the diagnostics of the Ex power module in RUN without affecting the
system.
Changing parameters in RUN
The parameters are transferred to the Ex power module with the "WRREC" instruction via data
record 128.
The parameters set in STEP 7 are not changed in the CPU, which means that the parameters set
in STEP 7 will be valid again after a restart.
Output parameter STATUS
If errors occur when transferring parameters with the "WRREC" instruction, the Ex power module
continues operation with the previous parameter assignment. The STATUS output parameter
contains the corresponding error code.
The STATUS output parameter is 4 bytes long and is configured as followed:
• Byte1: Function_Num, general error code
• Byte2: Error_Decode, location of the error code
• Byte3: Error_Code_1, error code
• Byte4: Error_Code_2, manufacturer-specific extension of the error code
Module-specific errors of the Ex power module are displayed via Error_Decode = 0x80 and
Error_Code_1 / Error_Code_2.
Error_
Error_
Cause
Code_1
Code_2
0xB0
Variable Number of the data record unknown (Er‐
ror_Code_2 returns internal identifiers)
0xB1
0x01
Length of the data record is incorrect
0xB2
Variable Ex power module cannot be reached (Er‐
ror_Code_2 returns internal identifiers)
0xE0
0x01
Header error (version or defined bits incorrect)
Modules for devices in a hazardous area
System Manual, 04/2021, A5E50165138-AA
Remedy
Enter valid number for data record.
Enter valid value for data record length.
Check station - is the module plugged in correctly?
Check the parameters of the WRREC instruction.
Correct the version number or defined bits.