Technical specifications
11.4 Mechanical and climatic environmental conditions
Climatic environmental conditions
The following table shows the permissible climatic ambient conditions for the components of
the Ex module group.
Table 11-5
Climatic environmental conditions
Ambient conditions
Temperature
(Use with ET 200SP HA)
Temperature
(Use with ET 200SP)
Air pressure
Relative humidity
Concentration of pollu‐
tants
108
Permissible range
Horizontal installation: from -40 °C to
70 °C
Vertical installation: from -40 °C to
60 °C
Horizontal installation: from -30 °C to
60 °C
Vertical installation: from -30 °C to
50 °C
From 1080 hPa
(corresponds to a depth of approxi‐
mately -1000 m)
Up to 795 hPa
(corresponds to an elevation of approx‐
imately 2000 m)
From 10 to 95%
Max. 95% at +25 °C
SO
: <0.5 ppm
2
RH: <60 %, no condensation
H
S: <0.1 ppm
2
RH: <60 %, no condensation
ISA-S71.04 severity level G1; G2; G3
Comments
Observe the following "Derating" table and any load-
dependent limitations.
Refer to the documentation of the employed compo‐
nent.
The cooling effect of air depends on the density of the
air. The locally occurring air pressure (operating alti‐
tude) might restrict the maximum permissible ambi‐
ent temperature. The density of the air decreases with
increasing altitude.
Derating for the Ex power module (Page 114)
Without condensation, corresponds to relative humid‐
ity (RH) stress grade 2 in accordance with
EN / IEC 61131 part 2
Test: 10 ppm; 4 days
Test: 1 ppm; 4 days
All assembled PCBs are treated with protective lacquer.