Siemens SIMATIC ET 200SP HA Manual
Siemens SIMATIC ET 200SP HA Manual

Siemens SIMATIC ET 200SP HA Manual

Digital input module di 8x24...125vdc
Hide thumbs Also See for SIMATIC ET 200SP HA:

Advertisement

Quick Links

SIMATIC
ET 200SP HA
Digital input module DI
8x24...125VDC HA
(6DL1131-6DF00-0PK0)
Manual
11/2017
A5E39288633-AB
Security information
Product overview
Wiring
Parameters
Displays and interrupts
Technical specifications
Drivers, parameters,
diagnostics messages and
address space
1
2
3
4
5
6
A

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIMATIC ET 200SP HA

  • Page 1 Security information Product overview Wiring SIMATIC Parameters ET 200SP HA Digital input module DI Displays and interrupts 8x24...125VDC HA (6DL1131-6DF00-0PK0) Technical specifications Manual Drivers, parameters, diagnostics messages and address space 11/2017 A5E39288633-AB...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    Table of contents Security information............................5 Product overview............................7 Properties of the I/O module DI 8x24…125VDC HA..............7 Wiring................................9 Pin assignment of the I/O module DI 8x24…125VDC HA............9 Schematic circuit diagram......................11 Parameters..............................13 Parameters of the I/O module DI 8x24…125VDC HA............13 Module/channel parameters....................14 Explanation of the module/channel parameters..............16 Displays and interrupts..........................17 Status and error displays of the I/O module DI 8x24…125VDC HA........17 Interrupts..........................20...
  • Page 4 Table of contents Digital input module DI 8x24...125VDC HA (6DL1131-6DF00-0PK0) Manual, 11/2017, A5E39288633-AB...
  • Page 5: Security Information

    Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber...
  • Page 6 Security information Conventions Please also observe notes marked as follows: Note A note contains important information on the product described in the documentation, on the handling of the product and on the section of the documentation to which particular attention should be paid.
  • Page 7: Product Overview

    Product overview Properties of the I/O module DI 8x24…125VDC HA [ID: 80184473739] View of the module 8x 24 ..1 25 VD C DI AG M T 1 DI .0 + DI .1+ 3 DI .2+ DI .3 + 5 DI .4 + 7 DI .6 + DI .5 + DI .7+...
  • Page 8 Product overview 2.1 Properties of the I/O module DI 8x24…125VDC HA Properties The I/O module has the following technical properties: ● 8 digital inputs electrically isolated from the backplane bus and supply voltage L+/M groups of 8 ● Digital input with the following parameterizable properties –...
  • Page 9: Wiring

    Wiring Pin assignment of the I/O module DI 8x24…125VDC HA [ID: 80184505355] Terminal blocks You can operate the I/O module with the following terminal blocks: ● 6DL1193-6TP00-0DK0, light-colored ● 6DL1193-6TP00-0BK0, dark-colored The terminal block is not included in the scope of delivery of the I/O module and must be ordered separately.
  • Page 10 Wiring 3.1 Pin assignment of the I/O module DI 8x24…125VDC HA General pin assignment Table 3-1 Terminal assignment of the DI 8×24...125VDC HA Terminal Assignment Terminal Assignment Explanations : Input signal, channel n 2M: Signal voltage 1P1: Supply voltage L+ of the voltage bus 1P 2P1: Supply voltage L+ of the voltage bus 2P 1P2: Ground reference of the voltage bus 1P 2P2: Ground reference of the voltage bus 2P...
  • Page 11: Schematic Circuit Diagram

    Wiring 3.2 Schematic circuit diagram Schematic circuit diagram [ID: 80184569227] The following figure shows the schematic circuit diagram of the DI 8x24...125VDC HA. DIAG Status Channel 0...7 Status Diagnostics Error channel 0 Error channel 7 Voltage 24 V DC 3.3 V monitoring Reverse polarity protection Figure 3-1...
  • Page 12 Wiring 3.2 Schematic circuit diagram Table 3-2 Dependencies of nominal input voltage und resistor Nominal input voltage Resistor Rs 24 V DC 43 kΩ 48 V DC 100 kΩ 125 V DC 300 kΩ Digital input module DI 8x24...125VDC HA (6DL1131-6DF00-0PK0) Manual, 11/2017, A5E39288633-AB...
  • Page 13: Parameters

    Parameters Parameters of the I/O module DI 8x24…125VDC HA [ID: 80184625803] Configuring You configure the I/O module with PCS 7 V9.0 or higher. Parameters You define the functioning of the I/O module via parameters. The time stamp (accuracy 1 ms) is configured in the parameter dialog of the I/O module. The parameters are subdivided into: ●...
  • Page 14: Module/Channel Parameters

    Parameters 4.2 Module/channel parameters Module/channel parameters [ID: 91143428107] Parameters of the DI 8x24…125VDC HA You have the following setting options: Table 4-1 Parameters and their default settings Parameters Value range Default Parameter re‐ Efficiency range assignment in Diagnostics, Enabled Module ●...
  • Page 15 Parameters 4.2 Module/channel parameters See also Schematic circuit diagram (Page 11) Digital input module DI 8x24...125VDC HA (6DL1131-6DF00-0PK0) Manual, 11/2017, A5E39288633-AB...
  • Page 16: Explanation Of The Module/Channel Parameters

    Parameters 4.3 Explanation of the module/channel parameters Explanation of the module/channel parameters [ID: 80184636939] Operating mode Specifies whether a channel is activated or deactivated. Diagnostics, Missing supply voltage L+ Enabling of the diagnostics for missing or insufficient supply voltage L+. Diagnostics, Wire break If wire-break check is activated and in the event of insufficient current flow at the input, you can enable wire-break diagnostics via the parameter Diagnostics wire break.
  • Page 17: Displays And Interrupts

    Displays and interrupts Status and error displays of the I/O module DI 8x24…125VDC HA [ID: 80184678667] LED displays The following figure shows the LED displays of the I/O module. 8x24..125VDC DIAG MT 1 DI.0+ DI.1+ 3 DI.2+ DI.3+ 5 DI.4+ DI.5+ 7 DI.6+ DI.7+...
  • Page 18 Displays and interrupts 5.1 Status and error displays of the I/O module DI 8x24…125VDC HA DIAG LED Table 5-1 Diagnostics display of the DIAG LED DIAG LED Meaning The power supply of the ET 200SP HA is faulty or switched off. Module is not configured.
  • Page 19 Displays and interrupts 5.1 Status and error displays of the I/O module DI 8x24…125VDC HA Channel status Channel fault Meaning Process signal = 0 and ● Channel enabled and channel diagnostics pending Process signal = 1 and ● Channel enabled and channel diagnostics pending PWR LED Table 5-4 Status display of the PWR LED...
  • Page 20: Interrupts

    Displays and interrupts 5.2 Interrupts Interrupts [ID: 80184722827] The I/O module supports diagnostic interrupts and hardware interrupts. You can find additional information on hardware interrupts in the appendix Hardware interrupts (Page 34) Diagnostics interrupts Diagnostics interrupts are used by the I/O module to output both diagnostic messages and maintenance events;...
  • Page 21: Technical Specifications

    Technical specifications [ID: 80184746251] Technical data of DI 8×24...125VDC HA Article number 6DL1131-6DF00-0PK0 General information Product type designation DI 8x24 ... 125VDC HA HW functional status FS01 Firmware version V1.0 ● FW update possible Usable terminal block TB type K0 Color code for module-specific color identifica‐...
  • Page 22 Technical specifications Article number 6DL1131-6DF00-0PK0 Input characteristic curve in accordance with IEC 61131, type 1 Input characteristic curve in accordance with IEC 61131, type 3 Time stamping Yes; Resolution 10 ms Time stamp (with precision of 1 ms) Yes; Resolution 1ms Input voltage ●...
  • Page 23 Technical specifications Article number 6DL1131-6DF00-0PK0 ● between the channels and backplane bus Permissible potential difference between different circuits 250 V AC/300 V DC Isolation Isolation tested with 3 500 V DC/1 min, type test Ambient conditions Ambient temperature during operation -40 °C ●...
  • Page 24 Technical specifications Digital input module DI 8x24...125VDC HA (6DL1131-6DF00-0PK0) Manual, 11/2017, A5E39288633-AB...
  • Page 25: Drivers, Parameters, Diagnostics Messages And Address Space

    Drivers, parameters, diagnostics messages and address space Concept of the driver and diagnostics blocks [ID: 96680491787] Use outside the PCS 7 environment The following information of the appendix relates to the use of the ET 200SP HA outside the PCS 7 environment. If you do not plan to operate outside the PCS 7 environment, you do not need the information in the appendix.
  • Page 26 A.1 Concept of the driver and diagnostics blocks This block concept supports all modules from the list of approved modules. When new Siemens or non-Siemens module types are integrated, the meta-knowledge for the driver generator can be extended by additional XML files (object and action lists).
  • Page 27: Parameter Assignment

    Drivers, parameters, diagnostics messages and address space A.2 Parameter assignment Parameter assignment [ID: 80184760203] Parameter assignment in the user program You can reconfigure individual channels of the module in RUN without this having an effect on the other channels. Changing parameters in RUN The "WRREC"...
  • Page 28 Drivers, parameters, diagnostics messages and address space A.2 Parameter assignment Valid parameters Only the values specified in the following are permitted. Values that are not listed are rejected by the module. Every parameter data record is checked by the module. If an incorrect parameter is detected, the entire data record is rejected and the parameters of the module remain unchanged.
  • Page 29: Parameter Assignment And Structure Of The Module/Channel Parameters

    Drivers, parameters, diagnostics messages and address space A.3 Parameter assignment and structure of the module/channel parameters Parameter assignment and structure of the module/channel parameters [ID: 91015110795] Structure of data record 128 Data record 128 is 28 bytes long. It contains module parameters as well as all channel parameters of the 8 channels. Figure A-1 Structure of data record 128 Digital input module DI 8x24...125VDC HA (6DL1131-6DF00-0PK0)
  • Page 30 Drivers, parameters, diagnostics messages and address space A.3 Parameter assignment and structure of the module/channel parameters Header information and module parameters The following figure shows the structure of the header information and module parameters. Figure A-2 Header information and module parameters of data record 128 Channel parameters Every channel parameter block contains the channel parameters for the digital input (2 bytes).
  • Page 31 Drivers, parameters, diagnostics messages and address space A.3 Parameter assignment and structure of the module/channel parameters All unused bits and the bits or bytes marked as "reserved" must be set to zero. You activate a channel parameter by setting the corresponding bit to "1" or the corresponding value.
  • Page 32: Diagnostics Messages And Maintenance Events

    Drivers, parameters, diagnostics messages and address space A.4 Diagnostics messages and maintenance events Diagnostics messages and maintenance events [ID: 91008185867] Diagnostics messages A diagnostics message is generated for every fault identified. The DIAG LED on the module flashes. There is additionally a channel-specific display of the diagnostics through the corresponding channel fault LEDs The diagnostic messages can, for example, be read from the diagnostic buffer of the CPU.
  • Page 33 Drivers, parameters, diagnostics messages and address space A.4 Diagnostics messages and maintenance events Diagnostics mes‐ Error Assignment Meaning Solution sage code Retentive memo‐ Module A memory block fault on the support Replace carrier module ry in carrier mod‐ module was detected during start-up ule defective Retentive memo‐...
  • Page 34: Hardware Interrupts

    Drivers, parameters, diagnostics messages and address space A.5 Hardware interrupts Hardware interrupts [ID: 91008194059] Hardware interrupts The DI 8x24…125VDC HA can trigger hardware interrupts on a signal change of digital inputs. Interrupt OBs are called automatically if an interrupt occurs. You can find detailed information on the event in the hardware interrupt organization block with the "RALRM"...
  • Page 35: Address Space

    Drivers, parameters, diagnostics messages and address space A.6 Address space Address space [ID: 80184647691] Abbreviations ● "IB" stands for input byte, that is, the module start address in the input area ● "DI" stands for digital input ● "QDIn" stands for the value status (QI) of digital input n Address space The following figures shows the assignment of the address space of the DI 8×24...125VDC IB x +...
  • Page 36: Address Space Of The Time Stamping (Accuracy 1 Ms)

    Drivers, parameters, diagnostics messages and address space A.7 Address space of the time stamping (accuracy 1 ms) Address space of the time stamping (accuracy 1 ms) [ID: 91907821067] Abbreviations ● "IB" stands for input byte, that is, the module start address in the input area ●...
  • Page 37: Index

    Index Channel fault LED, 17 Technology parameters, 29 Channel parameters, 14, 29 Terminal block, 9 Channel status LED, 17 Conventions, 6 Value status Evaluating, 35, 36 Data record 128, 29 Header information, 30 DI 8x24…125VDC HA Accessories, 8 Channel parameters, 14 Functions, 8 Module parameters, 14 Parameters, 13, 14...
  • Page 38 Index Digital input module DI 8x24...125VDC HA (6DL1131-6DF00-0PK0) Manual, 11/2017, A5E39288633-AB...

Table of Contents