Technical specifications
11.7 Technical specifications of subcomponents of the Ex module group
Article number
Ex(i) characteristics
Module for Ex(i) protection
maximum values for connecting terminals for
gas group IIC
•
Potential separation
primary/secondary
Isolation
Isolation tested with
Ambient conditions
Ambient temperature during operation
•
•
Altitude during operation relating to sea level
•
Dimensions
Width
Height
Depth
Weights
Weight, approx.
11.7.3
Derating for the Ex power module
Maximum permissible output current for the Ex power module depending on the mounting
position and the ambient temperature.
Mounting position
Horizontal installation:
Vertical installation:
114
Um (voltage at non-intrinsically safe connect‐
ing terminals), max.
min.
max.
Installation altitude above sea level, max.
6DL1133-6PX00-0HW0
Yes
60 V
Yes
further information on insulation can be found in
the "ET 200SP HA / ET 200SP modules for devices in
hazardous areas" System Manual
-40 °C
70 °C; with derating
2 000 m
50 mm
114 mm
67.5 mm
182 g
Ambient temperature
from -40 °C to 60 °C
from -40 °C to 70 °C
from -40 °C to 50 °C
from -40 °C to 60 °C
Output current
0.8 A
0.6 A
0.8 A
0.6 A
Modules for devices in a hazardous area
System Manual, 04/2021, A5E50165138-AA