D.2 Cable cross-sections and ferrules
D.2

Cable cross-sections and ferrules

Cables with and without ferrule
The stripped part of the cable must be completely inserted into the terminal of the Ex BaseUnit.
Note
Cable cross-sections
The cable diameters must be approved for the required current.
Rule for ...
Permitted cable cross-sections for solid cables
Permitted cable cross-
Without ferrule
sections for flexible
cables
With wire end sleeves (with
plastic sleeve)***
With TWIN end sleeve***
Stripped length of the cables
Wire end sleeves in accordance with DIN 46228 with
plastic sleeve***
* AWG: American Wire Gauge
** Ferrules without plastic sleeve: 1.0 mm
*** See note on ferrules
Note
Ferrules
You can achieve optimal results with respect to a high-quality and durable electrical connection
and maximum conductor extraction forces at the same time by using crimping dies preferably
with smooth surfaces. Options include rectangular and trapezoidal crimping cross-sections.
Due to the large number of crimping dies used in the industry, we can recommend others on
request. Crimp forms with a pronounced wave profile are not permitted.
128
Ex power module (supply volt‐
1.0 to 2.5 mm
AWG*: 17 to 13
1.0 to 2.5 mm
AWG*: 17 to 13
1.0 to 1.5 mm
AWG*: 17 to 16
1 mm
2
8 to 10 mm
8 and 10 mm long
to 2.5 mm
/AWG: 17 to 13
2
2
age)
(Push‑in terminal of the Ex Base‐
2
2
AWG*: 24 to 14
2
**
0.14 mm to 1.5 mm
AWG*: 26 to 16
-
Modules for devices in a hazardous area
System Manual, 04/2021, A5E50165138-AA