Note
Adjacent components
To remove a specific Ex BaseUnit, you need to remove adjacent components (Ex BaseUnit or
server module) located on the right. If there is a clearance of approx. 8 mm to the adjacent
components on the right, you can remove the Ex BaseUnit.
Note
Module in Zone 2
In general, it is not allowed to pull or plug modules in Zone 2.
Before starting work, ensure that no explosive atmosphere is present and that the power supply
is switched off.
Procedure
Step
1
3
Modules for devices in a hazardous area
System Manual, 04/2021, A5E50165138-AA
Procedure
Press the mounting rail release at the top of the Ex Base‐
Unit
and move the Ex BaseUnit at least 8 mm to the
right
.
1. Keep the mounting rail release on the Ex BaseUnit
pressed
and swing the Ex BaseUnit out of the
mounting rail
.
2. Lift the Ex BaseUnit upwards from the mounting
rail
.
7.2 Removing the Ex module group
Illustration
Removal
77