Explosion Protection - Siemens SIMATIC ET 200SP HA System Manual

Modules for devices in a hazardous area
Hide thumbs Also See for SIMATIC ET 200SP HA:
Table of Contents

Advertisement

Use in the industrial environment
SIMATIC products are designed for use in industry.
Area of applica‐
tion
Industry
Use in residential areas
Note
The distributed I/O system is intended for use in industrial environments; when used in
residential areas, it can affect radio/television reception.
If you use the distributed I/O system in residential areas, you must ensure that the emission of
radio interference complies with EN / IEC 61000‑6‑3.
Suitable measures for achieving RF interference level Class B include, for example:
• Installation of the ET 200SP HA distributed I/O system in grounded control cabinets/boxes
• Use of filters in the supply lines
11.1.3

Explosion protection

Certification
The approved Ex I/O modules may be installed in the following areas in compliance with the
specific conditions of use:
• In the safe area
• In Zone 2 (category 3G)
The certificates of conformity and the explanations of the designations can be found on the
Internet
US).
ATEX Approval
Table 11-1
Type Examination Certificate Number
Standards
Marking for Ex-PM-E
Marking for Ex I/O modules
Modules for devices in a hazardous area
System Manual, 04/2021, A5E50165138-AA
Interference emission requirements Interference immunity requirements
EN / IEC 61000-6-4
(https://support.industry.siemens.com/cs/products?dtp=Certificate&mfn=ps&lc=en-
Certification according to the following standards:
Technical specifications
11.1 Standards and approvals
EN / IEC 61000-6-2
Several certificates
EN 60079-0
EN 60079-7
EN 60079-11
II 3 G (1) Ex ec [ia] IIC T4 Gc
II 3 G (1) G Ex ec [ia Ga] IIC T4 Gc
II 3 G (1) D Ex ec [ia IIIC Da] IIC T4 Gc
101

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic et 200sp

Table of Contents