Procedure
Replacing an Ex I/O module without changing the type (Page 86)
Table 9-3
Replacing an I/O module and changing the type
Step
Procedure
1
Perform change in runtime: Read section "Actions during operation - Overview (Page 83)".
2
Simultaneously press the two release buttons
the top and bottom of the Ex I/O module.
3
Hold down the release buttons and pull the Ex I/O
module towards the front and out of the slot
Avoid pulling out an Ex I/O module at a slanted angle.
4
Use a screwdriver to lift the coding element out of
the Ex BaseUnit.
5
Insert the coding element into the removed I/O mod‐
ule.
6
Insert the new Ex I/O module (different module
type) into the Ex BaseUnit until it audibly clicks
into place.
Label the new Ex I/O module.
Modules for devices in a hazardous area
System Manual, 04/2021, A5E50165138-AA
Illustration
on
.
Service and maintenance
9.4 Change Ex module group