5Accif01.Fplk-000 - B&R Automation PC 2200 User Manual

Hide thumbs Also See for Automation PC 2200:
Table of Contents

Advertisement

2.3.4.3 5ACCIF01.FPLK-000

2.3.4.3.1 General information
Interface option 5ACCIF01.FPLK-000 is equipped with 2 female RJ45 connectors; both connectors are connected
to an integrated POWERLINK hub. In addition, 512 kB nvSRAM is installed.
With the integrated 2-port hub, a simple tree structure, daisy chain wiring or optional ring redundancy can be easily
implemented without additional effort.
With poll-response chaining (PRC), the IF option offers a solution for the highest demands on response time and
the shortest cycle times. Especially for central control tasks, poll-response chaining in combination with the B&R
control system provides ideal performance.
• 1x POWERLINK interface for real-time communication
• 512 kB nvSRAM
• Integrated hub for economical wiring
• Configurable ring redundancy
• Poll-response chaining
• Compatible with APC2100/PPC2100 and APC2200/PPC2200
This interface option can only be operated with Automation Runtime.
Information:
Ring redundancy in combination with poll-response chaining is not possible at the same time with
this IF option.
2.3.4.3.2 Order data
Model number
Short description
Interface options
5ACCIF01.FPLK-000
Interface card - 1x POWERLINK interface - Integrated 2-port
hub - 512 kB nvSRAM - For APC2100/PPC2100/APC2200/
PPC2200 - Only available with a new device
2.3.4.3.3 Technical data
Information:
The following specified characteristic data, features and limit values are only valid for this accessory
and may differ from those of the complete system. The data specified for the complete system applies
to the complete system in which this accessory is installed, for example.
Model number
General information
LED status indicators
B&R ID code
Certifications
CE
UL
HazLoc
Controller
nvSRAM
Size
Data retention
Read/Write endurance
Remanent variables in power failure mode
Automation PC 2200 User's manual V 1.05 Translation of the original documentation
Table 85: 5ACCIF01.FPLK-000 - Order data
(for e.g. Automation Runtime, see Automation Help)
Table 86: 5ACCIF01.FPLK-000 - Technical data
5ACCIF01.FPLK-000
L1, L2, L3
0xE9BA
Yes
cULus E115267
Industrial control equipment
cULus HazLoc E180196
Industrial control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T4
512 kB
20 years
Min. 1,000,000
256 kB
Technical data
Figure
1)
81

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents