3.2 Installing the DC power cable

Danger!
The entire power supply to the B&R industrial PC or B&R Automation Panel must be interrupted. Before
connecting the DC power cable, it must be checked whether it has been disconnected from the voltage
source (e.g. power supply).

3.2.1 Wiring

Install the DC power cable on the terminal block (power supply connector) as shown in the figure below. Conductors
with a cross section of 0.75 mm
Installing screw clamp terminal block 0TB103.9
Secure the conductors with wire end sleeves in the terminal contacts ➁ as shown in the figure below and tighten
the screw clamp terminals ➀ with a screwdriver (tightening torque max. 0.4 Nm).
When wiring, pay attention to the pinout of the power supply connection on the device!
DC power cable
Installing cage clamp terminal block 0TB103.91
Insert a screwdriver into the cage clamp terminals ➀ and secure the conductors with wire end sleeves in the terminal
contacts ➁ as shown in the figure below. Close the terminal contact by removing the screwdriver.
When wiring, pay attention to the pinout of the power supply connection on the device!
DC power cable
Automation PC 2200 User's manual V 1.05 Translation of the original documentation
to 1.5 mm
and wire end sleeve must be used.
2
2
24 VDC
Functional ground
0 VDC
Terminal contacts
Figure 34: Installing a screw clamp terminal block
24 VDC
Functional ground
0 VDC
Terminal contacts
Figure 35: Installing a cage clamp terminal block
Screw clamp terminals
+
-
Terminal block
Cage clamp terminals
Terminal block