Technical data

2.3.4 Interface options

Information:
Interface options can only be installed and replaced at the B&R factory.

2.3.4.1 5ACCIF01.FPCC-000

2.3.4.1.1 General information
Interface option 5ACCIF01.FPCC-000 is equipped with a POWERLINK interface, 2 CAN bus master interfaces
and an X2X Link master interface. In addition, 512 kB nvSRAM is installed.
• 1x POWERLINK interface managing or controlled node
• 2x CAN bus master interfaces
• 1x X2X Link master interface
• 512 kB nvSRAM
• Compatible with APC2100/PPC2100 and APC2200/PPC2200
This interface option can only be operated with Automation Runtime.
2.3.4.1.2 Order data
Model number
Short description
Interface options
5ACCIF01.FPCC-000
Interface card - 2x CAN interfaces - 1x X2X Link interface -
1x POWERLINK interface - 512 kB nvSRAM - For APC2100/
PPC2100/APC2200/PPC2200 - Only available with a new de-
vice
Optional accessories
Terminal blocks
0TB1210.3100
Connector 300 VDC - 10-pin female - Cage clamp terminal block
- Protected against vibration by the screw flange
2.3.4.1.3 Technical data
Information:
The following specified characteristic data, features and limit values are only valid for this accessory
and may differ from those of the complete system. The data specified for the complete system applies
to the complete system in which this accessory is installed, for example.
Model number
General information
LED status indicators
B&R ID code
Certifications
CE
UL
HazLoc
DNV GL
Controller
nvSRAM
Size
Data retention
Read/Write endurance
Remanent variables in power failure mode
66
Table 51: 5ACCIF01.FPCC-000 - Order data
(for e.g. Automation Runtime, see Automation Help)
Table 52: 5ACCIF01.FPCC-000 - Technical data
Automation PC 2200 User's manual V 1.05 Translation of the original documentation
5ACCIF01.FPCC-000
L1, L2, L3
0xE9BD
Yes
cULus E115267
Industrial control equipment
cULus HazLoc E180196
Industrial control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T4
Temperature: B (0 - 55 °C)
Humidity: B (up to 100%)
Vibration: A (0.7 g)
EMC: B (bridge and open deck)
512 kB
20 years
Min. 1,000,000
256 kB
Figure
1)
2)

Hide quick links: