Accessories

6.3 Terminal block for IF options

6.3.1 0TB1210.3100

6.3.1.1 General information

2-row 10-pin terminal block TB1210 is used to connect to the interfaces of various interface options.

6.3.1.2 Order data

Model number
Short description
Terminal blocks
0TB1210.3100
Connector 300 VDC - 10-pin female - Cage clamp terminal block
- Protected against vibration by the screw flange

6.3.1.3 Technical data

Information:
The following specified characteristic data, features and limit values are only valid for this accessory
and may differ from those of the complete system. The data specified for the complete system applies
to the complete system in which this accessory is installed, for example.
Model number
General information
Certifications
CE
UL
HazLoc
DNV GL
Terminal block
Note
Number of pins
Type of terminal block
Cable type
Spacing
Connection cross section
AWG wire
Wire end sleeves with plastic covering
Solid wires
Fine strand wires
With wire end sleeves
Electrical characteristics
Nominal voltage
Nominal current
3)
Operating conditions
Pollution degree per EN 61131-2
1)
Yes, but applies only if all components installed in the complete system have this certification and the complete system bears the corresponding mark.
2)
Yes, but applies only if all components installed in the complete system have this certification and are listed on the associated DNV GL certificate for the
product family.
3)
The respective limit data of the I/O modules must be taken into account!
184
Table 209: 0TB1210.3100 - Order data
Table 210: 0TB1210.3100 - Technical data
Automation PC 2200 User's manual V 1.05 Translation of the original documentation
0TB1210.3100
Yes
cULus E115267
Industrial control equipment
cULus HazLoc E180196
Industrial control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T4
Temperature: B (0 - 55 °C)
Humidity: B (up to 100%)
Vibration: A (0.7 g)
EMC: B (bridge and open deck)
Nominal data per UL
10 (female)
Push-in spring connection
Only copper wires (no aluminum wires!)
3.5 mm
26 to 16 AWG
0.14 to 1 mm²
0.14 to 1.5 mm²
0.14 to 1.5 mm²
0.14 to 1.5 mm²
300 V
10 A
Pollution degree 2
Figure
1)
2)