4
Option Components
◆
Option
A - Connector (CN5)
B - Installation hole
C - LED (MS)
*1
D - LED (NS)
*1
*1
Refer to
Option LED States on page 11
*2
Connect the included ground wire during installation. The ground wire is not necessary for installation on GA700 and GA800 drives.
◆
Terminal block CN1
The communication terminal is a pluggable terminal block that serves as the connection point of the DeviceNet
network communication cable to the option.
Terminal
◆
Option LED States
The option has two bicolor LEDs:
• Module status (MS)
• Network status (NS)
A - 1000-Series, Z1000U
B - GA500, GA700, and GA800
*1
LED label has transparent background and white letters. Please make sure that you use the correct label for FP605. The LED label for
FP605 drives is packaged with the FP605 drive.
Wait 2 seconds minimum for the power-up diagnostic process to complete before you verify the LED states.
The
Table 4.2
shows the operating status of the option LEDs after the power-up diagnostic LED sequence is
complete.
Refer to
Table 4.3
for more information about the LEDs.
YASKAWA SIEP C730600 84G DeviceNet Technical Manual
E - Ground terminal (FE) and installation hole
F - Terminal block CN1
G - Option model number
Figure 4.1 Option
for more information about the LEDs.
Table 4.1 Terminal Descriptions
Pin
Color
1
Black
2
Blue
3
-
4
White
5
Red
C - FP605
Figure 4.2 Option LED Labels
4 Option Components
Signal
V-
CAN_L
Shield
CAN_H
V+
*1
*2
Description
Network common
CAN data Low
Cable shield
CAN data High
Communications network
power DC +24V
11