Mounting/Connecting
4.2 Connecting
4.2.7

Inputs/outputs

Socket assignment
The digital inputs and output are equipped with standard 5-pin M12 sockets (A coding):
Assignment
Note
Potential transfer
With AS-i, digital inputs must not be connected to digital outputs because this can establish
an impermissible connection between the U
4.2.7.1

Digital inputs IN1 to IN4 (A coding)

The motor starters are equipped with four digital inputs, which you can connect directly to
sensors (PNP) (2 and 3-wire system).
Connectors (M12, 5-pin, A-coded) are used for this purpose. The motor starter is equipped
with a range of sockets.
Note
Short-circuit hazard
Do not use an external power supply since this can result in a short-circuit.
104
Pin
Input
1
+ 24 V (PWR+)
2
N/C
3
0 V (PWR-)
4
Input signal (IN x)
5
Functional ground (FE)
and U
AS-i
AUX
Output
N/C
N/C
0 V (PWR AUX-)
Output signal (OUT 1)
Functional ground (FE)
voltages.