Diagnostics
7.2 Diagnostics via parameter channel (parameter echo)
Call (motor starter M200D to AS-i master):
Parameter echo - warnings (W) / messages (M)
P3
0
0
0
0
0
1
1
1
1
1
1
1
1
Call (AS-i master to motor starter M200D):
P3
A/B switchover
1) automatically set by the system
Call (motor starter M200D to AS-i master):
Parameter echo - fault (F)
P3
0
0
0
0
0
0
1
1
1
1
1
1
See also
Assigning parameters using AS-i parameter bits (Page 115)
138
P2
P1
P0
0
0
0
0
0
1
0
1
0
0
1
1
1
0
0
0
0
0
0
0
1
0
1
0
0
1
1
1
0
0
1
0
1
1
1
0
1
1
1
P2
x (any state)
1)
P2
P1
P0
0
0
0
0
1
0
0
1
1
1
0
0
1
0
1
1
1
0
0
0
1
0
1
0
1
0
0
1
0
1
1
1
0
1
1
1
Decimal
Message/Warning
00
No warning/message
01
(M) No external startup parameters
received
02
(W) Main circuit breaker OFF
03
(W) Residual current warning
04
(M) Thermal motor model deactivated
08
(W) Overload
09
(W) Connector removed on line side
10
(M) Manual local control
11
(W) Prewarning limit of motor model
exceeded
12
(M) Temperature sensor deactivated
13
(W) Asymmetry warning
14
(W) Input action group warning
15
(W) Group warning
P1
x (any state)
Decimal
Fault
00
No fault
02
(F) Main circuit breaker OFF
03
(F) Residual current tripping
04
(F) Overload
05
(F) Device error
06
(F) No switching element supply voltage
09
(F) Connector removed on line side
10
(F) Electronics supply voltage too low
12
(F) Short-circuit trip
13
(F) Asymmetry tripping
14
(F) Invalid parameter value
15
(F) Group fault
P0
1
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004