Output n action
Different parameterizable actions can be triggered when an output signal is present.
Settings
Device parameter
Output 1 level
Output 1 signal
Output 1 action
Messages and actions
Output 1 active
Output overloaded
Output BO (brake output) active
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004
Default setting
Non-inverted
Continuous signal
Control source PIO DO2
(Slave 1)
Message
Setting range
Non-inverted
•
Inverted
•
Continuous signal
•
Flashing
•
Control by means of external control source
Control source PIO DO2 (Slave 1) (output)
•
Control source input 1
•
Control source input 2
•
Control source input 3
•
Control source input 4
•
Control via motor starter
Run-up
•
Operation/shunting
•
Coasting down
•
On time motor (RUN)
•
Control command motor ON
•
Brake output
•
Device ON (PWR-AUX)
•
Control by means of messages from the motor
starter
Group prewarning
•
Group warning
•
Group fault
•
Bus error
•
Device error
•
Ready for motor ON
•
Action
The output is controlled
Tripping (acknowledgment via trip reset)
The brake output is controlled
Functions
3.7 System monitoring
61