Siemens SIRIUS M200D Manual page 71

Industrial controls load feeders and motor starters
Hide thumbs Also See for SIRIUS M200D:
Table of Contents

Advertisement

The following message bits in diagnostics data set DS 200 clearly indicate which control
source currently has control priority:
● Automatic mode
● Manual mode local
– Integrated manual local control controls
– Input controls
● Connection abort in manual mode
Automatic
Manual
Manual mode bus
Automatic
Manual mode bus
mode
0
0
0
1
Connection monitoring
If the motor starter is controlled via the device interface (Motor Starter ES or hand-held
device), this connection is monitored. If this connection is interrupted, the motor starter trips
with the message "Connection abort in manual mode".
To exit this state, re-establish the connection and control again using the device interface.
Setting manual mode local for a local control station at the digital inputs
You can set manual mode local as follows:
● Parameterize the input n action as "Motor CW" or "Motor CCW" and the input n action of
another input as "Manual mode local".
● As long as the second input is active, the motor starter remains in "manual local" mode
and the motor can be controlled via the "Motor CW"/"Motor CCW" digital input.
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004
Manual mode local
Manual mode local Input control
0
1
0
1
0
1
0
0
Connection abort in
manual mode
0
0
0
1
1
0
0
0
Functions
3.9 Communication
Control priority
Integrated
manual local
control or local
device interface
None
Digital input
PLC (controller)
71