Offlline addressing with the addressing unit
The motor starter is addressed via the AS-i connection socket.
Note
When assigning the address via the addressing unit, unscrew the encoders (sensors) from
the digital inputs to prevent the addressing unit from being overloaded by their power
consumption.
If the older version of the addressing unit (3RK1904-2AB00) is used, a special addressing
cable (3RK1901-3RA00) is required to connect the module to the addressing unit.
1. Connect the motor starter to the addressing unit (3RK1904-2AB02) using a standard M12
2. Address the motor starter.
3. Unplug the addressing cable and reconnect the motor starter using the AS-i cable.
Online addressing with the AS-i master and in the PLC configuration software
For instructions on how to address the motor starter using the AS-i master or in the
configuration software, refer to the manual for the AS-i master you are using.
ID1 code
If required, set an ID1 code at this point as well.
This enables you to select a process image input assignment that is different from the default
setting. See Input process image (Page 120).
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004
connection cable (2 or 3-pin) (e.g. 3RK1902-4PB15-3AA0).
(4 or 5-pin connection cables must not be used for addressing purposes.)
Set the selector switch to ADDR.
Press
. The address of the connected motor starter is read and displayed.
Select the address by choosing
To transfer the address to the motor starter, choose
.
.
Mounting/Connecting
4.1 Mounting
95